Inspection item
Precautions for maintenance and inspection
7 - 2
7.1.3
Daily and periodic inspection
NOTE
When using the safety stop function, periodic inspection is required to confirm that safety func-
tion of the safety system operates correctly.
For more details, refer to the Safety stop function instruction manual (BCN-A23228-001).
Area of in-
spection
Inspection item
Description
Inspection
interval
Corrective action at
fault occurrence
Check by
the user
Da
ily
Pe
ri
od
ic
General
Surrounding
environment
Check the surrounding air temperature, humidity,
dirt, corrosive gas, oil mist, etc.
2
Improve the
environment.
Overall unit
Check for unusual vibration and noise.
2
Check fault location and
retighten.
Check for dirt, oil, and other foreign material.
2
Clean.
Power supply
voltage
Check that the main circuit voltages and control
voltages are normal.
2
Inspect the power
supply.
Main
circuit
General
(1) Check with megger (across main circuit
terminals and earth (ground) terminal).
2
Contact the
manufacturer.
(2) Check for loose screws and bolts.
2
Retighten.
(3) Check for overheat traces on the parts.
2
Contact the
manufacturer.
(4) Check for stain.
2
Clean.
Conductors, cables
(1) Check conductors for distortion.
2
Contact the
manufacturer.
(2) Check cable sheaths for breakage and
deterioration (crack, discoloration, etc.).
2
Contact the
manufacturer.
Transformer/reactor
Check for unusual odor and abnormal increase of
whining sound.
2
Stop the equipment and
contact the
manufacturer.
Terminal block
Check for a damage.
2
Stop the equipment and
contact the
manufacturer.
Smoothing
aluminium
electrolytic capacitor
(1) Check for liquid leakage.
2
Contact the
manufacturer.
(2) Check for safety valve projection and bulge.
2
Contact the
manufacturer.
(3) Visual check and judge by the life check of the
main circuit capacitor. (Refer to page 7-6.)
2
Relay/contactor
Check that the operation is normal and no
chattering sound is heard.
2
Contact the
manufacturer.
Control
circuit,
protective
circuit
Operation check
(1) Check that the output voltages across phases
are balanced while operating the inverter alone.
2
Contact the
manufacturer.
(2) Check that no fault is found in protective and
display circuits in a sequence protective
operation test.
2
Contact the
manufacturer.
C
o
mponen
ts
c
h
eck
Overall
(1) Check for unusual odor and discoloration.
2
Stop the equipment and
contact the
manufacturer.
(2) Check for serious rust development.
2
Contact the
manufacturer.
Aluminium
electrolytic
capacitor
(1) Check for liquid leakage in a capacitor and
deformation trace.
2
Contact the
manufacturer.
(2) Visual check and judge by the life check of the
control circuit capacitor. (Refer to page 7-6.)
2
Tab. 7-1:
Daily and periodic inspection (1)
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......