Copying and verifying parameters on the operation panel
Parameters
5 - 552
5.15.2 Parameter
verification
Whether the parameter settings of inverters are the same or not can be checked.
NOTES
●
appears... Why?
Parameter write error. Perform the operation from step
again.
●
and
are displayed alternately.
Appears when parameter copy is performed between inverters FR-F820-02330(55K) or lower
or inverters FR-F840-01160(55K) or lower and inverters FR-F820-03160(75K) or higher or FR-
F840-01800(75K) or higher.
When CP and 0.00 flicker alternately, set the Pr. 989 "Parameter copy alarm release" as shown
below (initial value):
After setting Pr. 989, perform setting of Pr. 9, Pr. 30, Pr. 51, Pr. 56, Pr. 57, Pr. 72, Pr. 80, Pr. 82, Pr.
90 to Pr. 94, Pr. 453, Pr. 455, Pr. 458 to Pr. 462, Pr. 557, Pr. 859, Pr. 860, and Pr. 893 again.
Operation
Copy the parameter settings of the verification source inverter to operation panel according to the procedure on page
5-551.
Move the operation panel to the inverter to be verified.
Screen at power-ON
The monitor display appears.
Parameter setting mode
Press
to choose the parameter setting mode. (The parameter number read previously appears.)
"
Selecting the parameter number
Turn
to
(parameter copy). Press
. "
" appears.
!
Parameter verification
Turn
to change to setting value "
" (parameter copy verification mode).
Press
. Verification of the parameter settings copied to the operation panel and the parameter settings of the
verification destination inverter is started. (It takes about 60 seconds to verify all the settings. During verification,
"
" flickers.)
If there are different parameters, the different parameter number and "
" flicker.
To continue verification, press
.
"
" and "
" flicker alternately after verification ends.
Tab. 5-290:
Parameter verification
NOTE
flickers... Why?
The set frequency may be incorrect. To continue verification, press SET key.
Pr. 989 setting Operation
10
Cancels the alarm of FR-F820-02330(55K) or lower and FR-F840-01160(55K) or lower.
100
Cancels the alarm of FR-F820-03160(75K) or higher and FR-F840-01800(75K) or higher.
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......