Precautions for use of the inverter
Power-OFF and magnetic contactor (MC)
FR-F800
3 - 17
3.4
Power-OFF and magnetic contactor (MC)
Inverter input side magnetic contactor (MC)
On the inverter input side, it is recommended to provide an MC for the following purposes:
(Refer to page 2-4 for selection.)
●
To disconnect the inverter from the power supply at activation of a protective function or at
malfunctioning of the driving system (emergency stop, etc.).
●
To prevent any accident due to an automatic restart at power restoration after an inverter stop
made by a power failure.
●
To separate the inverter from the power supply to ensure safe maintenance and inspection work.
If using an MC for emergency stop during operation, select an MC regarding the inverter input side
current as JEM1038-AC-3 class rated current.
As shown below, always use the start signal (ON or OFF of STF(STR) signal) to make a start or stop.
When the power supply is 400 V class, install a stepdown transformer.
Connect the power supply terminals R1/L11, S1/L21 of the control circuit to the input side of the
MC to hold an alarm signal when the inverter's protective circuit is activated. At this time, remove
jumpers across terminals R/L1 and R1/L11 and S/L2 and S1/L21. (Refer to page 2-54 for removal of
the jumper.)
쑶
NOTE
Since repeated inrush currents at power ON will shorten the life of the converter circuit (switching
life is about 1,000,000 times), frequent starts and stops of the magnetic contactor must be
avoided. Turn ON/OFF the inverter start controlling terminals (STF, STR) to run/stop the inverter.
Example
쑴
Inverter start/stop circuit example
I002424E
Fig. 3-12:
Start and stop of the inverter
MCCB
RA
U
V
A1
B1
C1
W
SD
MC
STF/STR
R/L1
S/L2
T/L3
R1/L11
S1/L21
MC
RA
MC
RA
MC
T
Inverter
To the
motor
Operation preparation
OFF
ON
Stop
Start-/Stop
Power
supply
Start
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......