24
Main circuit terminal specifications
(3) Total wiring length
Under general-purpose motor control
Connect one or more general-purpose motors within the total wiring length shown in the following table.
200V class
400V class
When driving a 400V class motor by the inverter, surge voltages attributable to the wiring constants may occur at the
motor terminals, deteriorating the insulation of the motor.
If that is the case,
use a "400V class inverter-driven insulation-
enhanced motor" and set a frequency in
Pr. 72 PWM frequency selection
according to the total wiring length shown in the
following table. (
Refer to page 52
to drive a 400V class motor with an inverter.)
Under IPM motor control
Use the following length of wiring or shorter when connecting an IPM motor.
Use one dedicated IPM motor for one inverter. Multiple IPM motors cannot be connected to an inverter.
Pr. 72 PWM frequency selection
Setting
(carrier frequency)
0.4K
0.75K
1.5K
or higher
1 (1kHz) or less
300m
500m
500m
2 to 15
(2kHz to 14.5kHz)
200m
300m
500m
Pr. 72 PWM frequency selection
Setting
(carrier frequency)
0.4K
0.75K
1.5K
2.2K
3.7K
or higher
1 (1kHz) or less
200m
200m
300m
500m
500m
2 to15
(2kHz to 14.5kHz)
30m
100m
200m
300m
500m
Total wiring length when using a general-purpose motor
(FR-F720PJ-1.5K or higher, FR-F740PJ-3.7K or higher)
Wiring Length
50m or less
50m to 100m
Exceeding 100m
Pr. 72 PWM frequency selection
Setting
(carrier frequency)
15 (14.5kHz) or less
8 (8kHz) or less
2 (2kHz) or less
Pr. 72 PWM frequency selection
Setting
(carrier frequency)
400V class 0.4K
200V class 0.4K or higher
400V class 0.75K or higher
4 (2.5kHz) or less
50m
100m
5 (5kHz) or higher
30m
NOTE
Especially for long-distance wiring, the inverter may be affected by a charging current caused by the stray
capacitances of the wiring, leading to a malfunction of the overcurrent protective function, fast-response current limit
function, or stall prevention function or a malfunction or fault of the equipment connected on the inverter output side.
If malfunction of fast-response current limit function occurs, disable this function.
If malfunction of stall prevention function occurs, increase the stall level.
(Refer to page 96 for Pr. 22 Stall prevention operation level
and
Pr. 156 Stall prevention operation selection )
When using the automatic restart after instantaneous power failure function for a general-purpose motor with the
wiring length longer than 100m, select "without frequency search" by setting
Pr.162
= "1 or 11."
The surge voltage suppression filter (FR-ASF-H/FR-BMF-H) option cannot be used under IPM motor control, so do
not connect them.
Parameters referred to
Pr.72 PWM frequency selection
300m+300m=600m
500m or less
300m
300m