Causes and corrective actions
Operation panel
indication
E.PE
FR-PU04
FR-PU07
Corrupt Memry
Name
Parameter storage device fault (control circuit board)
Description
Appears when a fault occurred in the stored parameters. (EEPROM fault)
Check point
Check for too many number of parameter write times.
Corrective action
Please contact your sales representative.
When performing parameter write frequently for communication purposes, set "1" in
Pr. 342
to enable RAM write. Note
that powering OFF returns the inverter to the status before RAM write.
Operation panel
indication
E.PUE
FR-PU04
FR-PU07
PU Leave Out
Name
PU disconnection
Description
This function stops the inverter output if communication between the inverter and PU is suspended, e.g. the
parameter unit (FR-PU04/FR-PU07) is disconnected, when "2", "3", "16" or "17" was set in
Pr. 75 Reset selection/
disconnected PU detection/PU stop selection
.
This function stops the inverter output when communication errors occurred consecutively for more than permissible
number of retries when a value other than "9999" is set in
Pr. 121 Number of PU communication retries
during the RS-
485 communication with the PU connector. (Use
Pr. 502 Stop mode selection at communication error
to change.)
This function also stops the inverter output if communication is broken within the period of time set in
Pr. 122 PU
communication check time interval
during the RS-485 communication with the PU connector.
Check point
Check that the parameter unit cable is connected properly.
Check the
Pr. 75
setting.
Check that RS-485 communication data is correct. And check that the settings of communication parameter at
inverter match settings of the computer.
Check that data is transmitted from the computer within a time set in
Pr. 122
PU communication check time interval
.
Corrective action
Connect the parameter unit cable securely.
Check the communication data and communication settings.
Increase the
Pr. 122 PU communication check time interval
setting. Or set "9999" (no communication check).
Operation panel
indication
E.RET
FR-PU04
FR-PU07
Retry No Over
Name
Retry count excess
Description
If operation cannot be resumed properly within the number of retries set, this function trips the inverter.
This function is available only when
Pr. 67
Number of retries at fault occurrence
is set.
When the initial value (
Pr. 67
= "0") is set, this protective function is not available.
Check point
Find the cause of fault occurrence.
Corrective action
Eliminate the cause of the error preceding this error indication.
Operation panel
indication
E.5
FR-PU04
FR-PU07
Fault 5
E.CPU
CPU Fault
Name
CPU fault
Description
Stops the inverter output if the communication fault of the built-in CPU occurs.
Check point
Check for devices producing excess electrical noises around the inverter.
Corrective action
Take measures against noises if there are devices producing excess electrical noises around the inverter.
Please contact your sales representative.
Operation panel
indication
E.CDO
FR-PU04
Fault 14
FR-PU07
OC detect level
Name
Output current detection value exceeded
Description
This function is activated when the output current exceeds the
Pr. 150 Output current detection level
setting.
Check point
Check the settings of
Pr. 150 Output current detection level
,
Pr. 151 Output current detection signal delay time
,
Pr. 166 Output
current detection signal retention time
,
Pr. 167 Output current detection operation selection
Operation panel
indication
E.IOH
FR-PU04
Fault 14
FR-PU07
Inrush overheat
Name
Inrush current limit circuit fault
Description
This function is activated when the resistor of the inrush current limit circuit overheats. The inrush current limit circuit fault
Check point
Check that frequent power ON/OFF is not repeated.
Corrective action
Configure a circuit where frequent power ON/OFF is not repeated.
If the problem still persists after taking the above measure, please contact your sales representative.