18
Wiring
2.1 Wiring
2.1.1
Terminal connection diagram
NOTE
To prevent a malfunction caused by noise, separate the signal cables more than 10cm from the power cables. Also
separate the main circuit wire of the input side and the output side.
After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting holes
in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
The terminals S1, S2, SC, and SO are for manufacturer setting. Do not remove the shortening wires across the
terminals S1 and SC and the terminals S2 and SC.
Earth
(Ground)
Motor
M
Earth (Ground)
Three-phase
AC power
supply
MCCB
MC
R/L1
P1
P/+
PR N/-
S/L2
T/L3
U
V
W
Earth
(Ground)
*7 Brake resistor (FR-ABR, MRS type, MYS type)
Install a thermal relay to prevent an overheat
and burnout of the brake resistor.
Always install a thermal relay when using a
brake resistor whose capacity is 11K or higher.
*8 It is not necessary when
calibrating the indicator
from the operation panel.
Forward
rotation start
Reverse
rotation start
Middle
speed
High
speed
Control input signals (No voltage input allowed)
24VDC power supply
(Common for external power supply transistor)
Contact input common
STR
STF
RH
RM
AU
SD
PC
Relay output
Running
Open collector output
Open collector output common
Sink/source common
RUN
SE
A
B
C
Frequency setting signals (Analog)
2 0 to 5VDC
10(+5V)
2
3
1
4 4 to 20mADC
Frequency
setting
potentiometer
1/2W1k
Ω
Terminal 4
input
(Current
input)
(+)
(-)
5(Analog common)
*5 It is recommended to
use 2W1k
Ω
when the
frequency setting signal
is changed frequently.
*5
*3 When using terminals PC-
SD as a 24VDC power
supply, take care not to
short across terminals
PC and SD.
PU
connector
*2
. DC reactor (FR-HEL)
When connecting a DC reactor, remove the
jumper across P1 and P/+.
Jumper
*2
*7
*3
*4
*6
Multi-speed selection
Terminal functions vary by
Pr. 190 RUN terminal function
selection
Terminal functions vary
by
Pr. 192
A,B,C terminal
function selection
SINK
SOURCE
V
I
*6
0 to 5VDC
(0 to 10VDC)
0 to 10VDC
*6 Terminal input specifications can be changed by analog
input specifications switchover (
Pr. 267
). Set the
voltage/current input switch in the "
V
" position to select
voltage input (0 to 5V/0 to10V) and "
I
" (initial value) to
select current input (4 to 20mA).
To use terminal 4 (initial setting is current input), set "4"
in any of
Pr.178 to Pr.182 (input terminal function
selection)
to assign the function, and turn ON AU signal.
Voltage/current
input switch
Main circuit
Control circuit
R
Relay output
(Fault output)
Brake unit
(Option)
FM
SD
Indicator
(Frequency meter, etc.)
+
-
Moving-coil type
1mA full-scale
Calibration resistor
*8
*4 Terminal input specifications
can be changed by analog
input specifications
switchover (
Pr. 73
).
Terminal 10 and terminal 2
are used as PTC input
terminal (
Pr. 561
).
Terminal 4
input
selection
Inrush current
limit circuit
24V
The function of these
terminals can be
changed to the reset
signal, etc. with the input
terminal assignment
(
Pr. 178 to Pr. 182
)
.
With Filterpack
Three-phase
AC power
supply
MCCB MC
R/L1
P1
P/+
S/L2
T/L3
Earth (ground)
*1 Remove the jumper
across the terminals P1
and P/+ to install
Filterpack.
Jumper
*1
R0
S0
T0
P1
P
Filterpack
FR-BFP2
GND
R
S
T
Control circuit terminal
Main circuit terminal
Sink logic