4.22.6 Initiating a fault (Pr.997)
(1)
Fault initiation (Pr. 997)
To initiate a fault, set the assigned number of the fault you want to initiate in
Pr. 997 Fault initiation
.
The value set in
Pr. 997 Fault initiation
is not stored in EEPROM.
When a fault occurs, the inverter trips, and the fault is output (ALM).
While the initiated fault is occurring, the fault is displayed as the latest fault in the faults history. After a reset, the faults
history goes back to the previous status. (The fault generated by the fault initiation function is not saved in the faults
history.)
Perform inverter reset to cancel the fault.
Setting for
Pr. 997 Fault initiation
and corresponding faults
A fault is initiated by setting the parameter.
This function is useful to check how the system operates at a fault.
Parameter
number
Name
Initial value
Setting range
Description
997
Fault initiation
9999
16 to 18, 32 to 34, 48, 49,
64, 81, 82, 96, 97, 112,
128, 129, 144, 145, 176 to
178, 192, 196, 197, 199,
201, 208, 230, 245
The setting range is same with the one for
fault data codes of the inverter (which can
be read through communication).
Written data is not stored in EEPROM.
9999
The read value is always "9999."
This setting does not initiate a fault.
The above parameters can be set when User group read selection=
"0".
.... Specifications differ according to the date assembled.
to check the SERIAL number.
REMARKS
If a fault is already occurring in the inverter, a fault cannot be initiated by
Pr. 997
.
The retry function is invalid for the fault initiated by the fault initiation function.
If another fault occurs after a fault has been initiated, the fault indication does not change.
The fault is not saved in the faults history either.
Setting (Data code)
Fault
16(H10)
E.OC1
17(H11)
E.OC2
18(H12)
E.OC3
32(H20)
E.OV1
33(H21)
E.OV2
34(H22)
E.OV3
48(H30)
E.THT
49(H31)
E.THM
64(H40)
E.FIN
81(H51)
E.UVT
82(H52)
E.ILF
96(H60)
E.OLT
97(H61)
E.SOT
112(H70)
E.BE
128(H80)
E.GF
129(H81)
E.LF
144(H90)
E.OHT
145(H91)
E.PTC
176(HB0)
E.PE
Setting (Data code)
Fault
177(HB1)
E.PUE
178(HB2)
E.RET
192(HC0)
E.CPU
196(HC4)
E.CDO
197(HC5)
E.IOH
199(HC7)
E.AIE
201(HC9)
E.SAF
208(HD0)
E.OS
230(HE6)
E.PID
245(HF5)
E.5
Setting (Data code)
Fault