225
Communication operation and setting
4.20.4 Communication EEPROM write selection (Pr. 342)
When changing the parameter values frequently, set "1" in
Pr. 342
to write them to the RAM only.
The life of the EEPROM will be shorter if parameter write is performed frequently with the setting unchanged from "0 (initial
value)" (EEPROM write).
REMARKS
The fault output indicates fault output signal (ALM signal) or alarm bit output.
When the setting was made to provide a fault output, the fault description is stored into the faults history. (The fault description
is written to the faults history when a fault output is provided.)
When no fault output is provided, the fault record overwrites the fault indication of the faults history temporarily, but is not
stored.
After the fault is removed, the fault indication returns to the ordinary monitor, and the faults history returns to the preceding fault
indication.
When the
Pr. 502
setting is "1, 2 or 3", the deceleration time is the ordinary deceleration time setting (e.g.
Pr. 8, Pr. 44, Pr. 45
). In
addition, acceleration time for restart is the normal acceleration time (e.g.
Pr. 7, Pr. 44
).
When "2 or 3" is set in
Pr. 502
, run command/speed command at restart follows the command before an fault occurrence.
When "2" is set in
Pr. 502
at occurrence of a communication error and the error is removed during deceleration, the inverter
accelerates again at that point.
If the communication error setting is disabled with
Pr. 502
= "3,"
Pr. 121
= "9999," and
Pr. 122
= "9999," the inverter does
not continue its operation with the frequency set by
Pr. 779
at a communication error.
If a communication error occurs while continuous operation at
Pr. 779
is selected with
Pr. 502
= "3," the inverter operates
at the frequency set in
Pr. 779
even though the speed command source is at the external terminals.
Example) If a communication error occurs while
Pr. 339
= "2" and the external terminal RL is ON, the operation is
continued at the frequency set in
Pr. 779
.
After a communication error has been removed while
Pr. 502
= "3," the inverter starts its operation in accordance with the
start and speed commands which were set before the error.
Parameters referred to
Pr. 7 Acceleration time, Pr. 8 Deceleration time
Pr. 190, Pr. 192 (output terminal function selection)
When parameter write is performed from RS-485 communication with the inverter PU connector, parameters storage
device can be changed from RAM to RAM only. Set when a frequent parameter change is necessary.
Parameter
Number
Name
Initial Value
Setting Range
Description
342
Communication EEPROM
write selection
0
0
Parameter values written by communication are
written to the EEPROM and RAM.
1
Parameter values written by communication are
written to RAM.
The above parameter can be set when
Pr. 160 Extended function display selection
= "0".
REMARKS
When "1" (write to RAM only) is set in
Pr. 342
, powering OFF the inverter will erase the changed parameter values. Therefore,
the parameter values available when power is switched ON again are the values stored in EEPROM previously.