191
Frequency setting by analog input (terminal 2, 4)
(b) Method to adjust any point without application of a voltage (current) across terminals 2
and
5 (4
and
5)
(To change from 4V (80%) to 5V (100%))
Operation Display
1.
Confirm the operation status indicator and
operation mode indicator
The inverter should be at a stop.
The inverter should be in the PU operation
mode.
(Use )
2.
Press
to choose the parameter setting
mode.
PRM indicator is lit.
(The parameter number read previously
appears.)
3.
Turn
until
appears.
4.
Press
to display
.
5.
Turn
until
(
) appears.
Set to
C4 Terminal 2 frequency setting gain
.
Terminal 2 input is
selected
Terminal 4 input
is selected
6.
Press
to display the analog voltage
(current) value (%).
Analog voltage (current)
value (%) across terminals 2
and 5 (across terminals 4
and 5)
7.
Turn
to set gain voltage (%).
"0V(0mA) is 0%, 10V(5V, 20mA) is 100%"
The gain frequency is
reached when the analog
voltage (current) value
across terminals 2 and 5
(across terminals 4 and 5) is
100%.
8.
Press
to set.
Terminal 2 input is
selected
Terminal 4 input is
selected
Flicker...Parameter setting complete!!
(Adjustment completed)
Turn
to read another parameter.
Press
to return to the
indication (step 4).
Press
twice to show the next parameter (
).
REMARKS
By pressing
after step 6, you can confirm the current frequency setting bias/gain setting.
You can not check after performing operation in step 7.
C0 to C25 settings
are enabled.
Hz
A
Hz
A
REMARKS
The current setting at the instant of turning
is
displayed.
You can not check after performing operation in step 7.
Hz
A
Hz
A