12. (M) Item and Output Signal for Monitoring
12.5 Energy saving monitoring
Estimated input power for the commercial power supply operation
(Pr.892, Pr.893, Pr.894)
• Select the pattern of the commercial power supply operation from among four patterns (discharge damper control (fan),
suction damper control (fan), valve control (pump) and commercial power drive), and set it in
Pr.894 Control selection
during commercial power-supply operation
.
• Set the motor capacity (pump capacity) in
Pr.893 Energy saving monitor reference (motor capacity)
.
• Refer to the following graph to find the rate of power consumption (%) during commercial power supply operation based
on the selected pattern and the rate of motor rotations per minute with respect to the rated speed (the result of dividing the
present output frequency by
Pr.3 Base frequency
setting).
• The estimated input power (kW) for the commercial power supply operation is calculated from the motor capacity set in
Pr.893
, the setting of
Pr.892 Load factor
, and the rate of power consumption using the following formula.
NOTE
• If the output frequency rises to the setting of
Pr.3 Base frequency
or higher, it stays at a constant value because the rotations
per minute cannot rise higher than the power supply frequency during commercial power supply operation.
Annual energy saving and its monetary value (Pr.899)
• When the operation time rate (ratio of the time period in year when the inverter drives the motor) [%] is set in
Pr.899
, the
annual energy saving effect can be estimated.
• When the inverter is operated in specific patterns, the estimate annual energy saving can be calculated by measuring the
energy saving in a certain period.
• Refer to the following procedure to set the operation time rate.
1.
Estimate the average operation time per day (h/day).
2.
Calculate the operation days per year (days/year) using the following formula: Average operation days per month ×
12 (months).
3.
Calculate the annual operation time (h/year) from values determined in Step 1 and Step 2, using the following
formula.
4.
Calculate the operation time rate using the following formula, and set it in
Pr.899
.
0
10
20
30
40
50
60
70
80
90
100
110
0 10 20 30 40 50 60 70 80 90100110
Ratio of speed to rating [%]
Discharge side
damper control
(fan)
Inlet damper control
(fan)
Valve control
(pump)
Commercial power-supply drive
Power consumption [%]
=
Pr.893
(kW) ×
Estimated consumed power during
commercial power supply operation (kW)
Consumed power (%)
×
Pr.892
(%)
100
100
Annual operation time (h/year) = average time (h/day) × number of operation days (days/year)
Operation time rate (%) =
Annual operation time (h/year)
× 100(%)
24 (h/day) × 365 (days/year)
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...