27
2. Basic Operation
2.2 Monitoring the inverter
1
2
3
4
5
6
7
8
9
10
2.2
Monitoring the inverter
2.2.1
Monitoring of output current and output voltage
• Press the SET key on the operation panel in the monitor mode to switch the monitor item between output frequency, output
current, and output voltage.
Operating procedure
1.
Press the MODE key during inverter operation to monitor the output frequency. The [Hz] LED turns ON.
2.
Press the SET key to monitor the output current. This operation is valid during running or stopping under any
operation mode. The [A] LED turns ON.
3.
Press the SET key to monitor the output voltage. Unit LEDs are both OFF.
NOTE
• Other monitor item, such as output power or set frequency, is also available. Use
Pr.52 Operation panel main monitor
selection
or
Pr.774 Operation panel monitor selection 1
to
Pr.776 Operation panel monitor selection 3
to change the
setting. (Refer to
.)
2.2.2
First priority monitor screen
The first priority monitor screen, which is displayed first when the operation panel becomes in the monitor mode, is selectable.
To set it, press the SET key for a while when the desired monitor item is displayed on a monitor screen.
The following show the procedure to set the monitor screen displaying the output current as the first priority monitor screen.
Operating procedure
1.
Change the mode of the operation panel to the monitor mode, and switch the monitor screen to the one on which
the output current can be monitored.
2.
Press the SET key for a while (1 second). The output current monitor screen is set as the first priority monitor screen.
3.
When the operation panel is in the monitor mode next time, the output current monitored value is displayed first.
NOTE
• Use
Pr.52 Operation panel main monitor selection
or
Pr.774 Operation panel monitor selection 1 to Pr.776 Operation
panel monitor selection 3
to change the monitor item. (Refer to
2.2.3
Displaying the set frequency
To display the present set frequency in the standard model, change the mode of the operation panel to the monitor mode and
press the setting dial (
) while the inverter runs in the PU operation mode or in the External/PU combined operation mode
1 (
Pr.79 Operation mode selection
= "3").
NOTE
• Use
Pr.992 Operation panel setting dial push monitor selection
to change the item to be displayed. (Refer to
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...