190
8. (E) Environment Setting Parameters
8.17 Maintenance timer alarm
8.17
Maintenance timer alarm
The Maintenance timer (Y95) signal is output when the inverter's cumulative energization time reaches the time period set with
the parameter. "MT" is displayed on the operation panel. This can be used as a guideline for the maintenance time of peripheral
devices.
• The cumulative energization time of the inverter is stored in the EEPROM every hour and displayed in
Pr.503
in 100 h
increments. The number indication on
Pr.503
stopped at 9998 (999,800 hours).
• When the value in
Pr.503
reaches the time (100 h increments) set in
Pr.504
, the Maintenance timer (Y95) signal is output,
and also "MT" is displayed on the operation panel.
• For the terminal used for the Y95 signal output, assign the function by setting "95" (positive logic) or "195" (negative logic)
in any parameter from
Pr.190 to Pr.196 (Output terminal function selection)
.
NOTE
• The cumulative energization time is counted every hour. Energization time of less than 1 h is not counted.
• Changing the terminal assignment using
Pr.190 to Pr.196 (Output terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.190 to Pr.196 (Output terminal function selection)
Pr.
Name
Initial value
Setting range
Description
503
E710
Maintenance timer
0
0 (1 to 9998)
Displays the inverter's cumulative energization time in
increments of 100 hours (read-only). Writing the setting of "0"
clears the cumulative energization time while
Pr.503
= "1 to
9998". (Writing is disabled when
Pr.503
= "0".)
504
E711
Maintenance timer warning
output set time
9999
0 to 9998
Set the cumulative energization time in 100 hours which
triggers the Maintenance timer (Y95) signal output.
9999
Without the function
First power
Time
ON
Maintenance
timer
(Pr. 503)
Set "0" in
Pr.503
Y95 signal
MT display
OFF
ON
ON
Pr.504
9998
(999800h)
Operation example of the maintenance timer
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...