186
8. (E) Environment Setting Parameters
8.16 Inverter parts life display
8.16
Inverter parts life display
The degree of deterioration of the control circuit capacitor, main circuit capacitor, cooling fan, and inrush current limit circuit can
be diagnosed on the monitor. When a part approaches the end of its life, an alarm can be output by self diagnosis to prevent
a fault. (Note that the life diagnosis of this function should be used as a guideline only, the life values are theoretical
calculations.)
Life alarm display and signal output (Y90 signal, Pr.255)
• In the life diagnosis of the main circuit capacitor, the Life alarm (Y90) signal is not output unless measurement by turning OFF
the power supply is performed.
•
Pr.255 Life alarm status display
and the Life alarm (Y90) signal can be used to check whether or not the life alarm output
level is reached for the following parts: the control circuit capacitor, main circuit capacitor, cooling fan, inrush current limit
circuit, relay contacts of terminals A, B, and C, inverter module, or control circuit board.
Pr.
Name
Initial value
Setting range
Description
198
E709
Display corrosion level
1
1 to 3
Displays the corrosion level of the control circuit board.
Read-only. (Available only for the FR-E8[][]-[]-60 (with
coating).)
255
E700
Life alarm status display
0
(0 to 879)
Displays whether or not the life alarm output level is
reached for the following parts: the control circuit
capacitor, main circuit capacitor, cooling fan, inrush
current limit circuit, relay contacts of terminals A, B, and
C, inverter module, and control circuit board. Read-
only.
256
E701
Inrush current limit circuit life
display
100%
(0% to 100%)
Displays the deterioration degree of the inrush current
limit circuit. Read-only.
257
E702
Control circuit capacitor life
display
100%
(0% to 100%)
Displays the deterioration degree of the control circuit
capacitor. Read-only.
258
E703
Main circuit capacitor life display
100%
(0% to 100%)
Displays the deterioration degree of the main circuit
capacitor. Read-only.
The value measured by
Pr.259
is displayed.
259
E704
Main circuit capacitor life
measuring
0
0, 1, (2, 3, 8, 9)
Setting "1" and turning the power supply OFF starts the
measurement of the main circuit capacitor life.
If the setting value of
Pr.259
becomes "3" after turning
the power supply ON again, it means that the
measurement is completed. The deterioration degree is
read to
Pr.258
.
506
E705
Display estimated main circuit
capacitor residual life
100%
(0% to 100%)
Displays the estimated residual life of the main circuit
capacitor. Read-only.
507
E706
Display ABC relay contact life
100%
0% to 100%
Displays the degree of deterioration of the relay
contacts of terminals A, B, and C.
509
E708
Display power cycle life
100%
(0% to 100%)
Displays the degree of deterioration of the inverter
module. Read-only.
bit0 Control circuit capacitor life
bit1 Main circuit capacitor life
bit2 Cooling fan life
bit3 Inrush current limit circuit life
bit5 Estimated residual-life of main circuit capacitor
bit6 Life of relay contacts of terminals A, B, and C
bit8 Life of the inverter module
bit9 Corrosion level
•
Pr.255
read
•
Pr.255
setting read
Bit image is displayed
in decimal
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 1
15
bit
7
0
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...