156
7. Adjustment during Real sensorless vector control, Vector control, PM sensorless vector control
7.3 Gain adjustment of current controllers for the d axis and the q axis
7.3
Gain adjustment of current controllers for the d
axis and the q axis
The gain of the current controller can be adjusted.
• Use
Pr.824 Torque control P gain 1 (current loop proportional gain)
to adjust the proportional gain of current
controllers for the d axis and the q axis. The 100% gain is equivalent to 1000 rad/s. Setting this parameter higher improves
the trackability for current command changes. It also reduces the current fluctuation caused by external disturbances.
• Use
Pr.825 Torque control integral time 1 (current loop integral time)
to set the integral time of current controllers for
the d axis and the q axis. If the setting value is small, it produces current fluctuation against external disturbances,
decreasing time until it returns to original current value.
NOTE
•
Pr.834 Torque control P gain 2 (current loop proportional gain) and Pr.835 Torque control integral time 2 (current loop
integral time)
are valid when the RT signal turns ON.
In this case, replace them for
Pr.824 and Pr.825
in the description above.
PM
PM
PM
Vector
Vector
Vector
Pr.
Name
Initial
value
Setting
range
Description
824
G213
Torque control P gain 1 (current
loop proportional gain)
100%
0% to 500%
The proportional gain of the current controller is set.
825
G214
Torque control integral time 1
(current loop integral time)
5 ms
0 to 500 ms
The integral time of the current controller is set.
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...