155
Monitor display and monitor output signal
P
ARAME
TERS
4.13.2 Monitor display selection of DU/PU and terminal FM
(Pr.52, Pr.54, Pr.170, Pr.171, Pr.268, Pr.430, Pr.563, Pr.564)
The monitor to be displayed on the main screen of the control panel and parameter unit (FR-PU07) can be selected.
In addition, signal to be output from the terminal FM (pulse train output) can be selected.
Parameter
number
Name
Initial value
Setting range
Description
52
DU/PU main display data
selection
0
(rotation speed
(output
frequency))
0, 5, 8 to 12, 14, 19,
20, 23 to 31, 36, 37,
52 to 55, 61, 62, 100
Select the monitor to be displayed on the
operation panel and parameter unit.
Refer to the following table for monitor
description.
54
FM terminal function
selection
1
(rotation speed
(output
frequency))
1 to 3, 5, 8 to 12, 14,
21, 24, 36, 37, 52, 53,
61, 62
Select the monitor output to terminal FM.
170
Watt-hour meter clear
9999
0
Set "0" to clear the watt-hour meter
monitor.
10
Sets the maximum value for the
monitoring from communication to
9999kWh.
9999
Sets the maximum value for the
monitoring from communication to
65535kWh.
171
Operation hour meter clear
9999
0, 9999
Set "0" in the parameter to clear the
operation time monitor.
Setting 9999 does not clear.
268
Monitor decimal digits
selection
9999
0
Displayed as integral value
1
Displayed in 0.1 increments.
9999
No function
430
Pulse monitor selection
9999
4
The lower 4 digits of the droop pulse [after
the electronic gear] is displayed.
5
The upper 4 digits of the droop pulse
[after the electronic gear] is displayed.
100
The lower 4 digits of the position
command [before the electronic gear] is
displayed.
101
The upper 4 digits of the position
command [before the electronic gear] is
displayed.
102
The lower 4 digits of the current position
[before the electronic gear] is displayed.
103
The upper 4 digits of the current position
[before the electronic gear] is displayed.
104
The lower 4 digits of the droop pulse
[before the electronic gear] is displayed.
105
The upper 4 digits of the droop pulse
[before the electronic gear] is displayed.
9999
The rotation speed (output frequency)
monitor is displayed.
563
Energization time carrying-
over times
0
0 to 65535
(reading only)
The numbers of cumulative energization
time monitor exceeded 65535h is
displayed. (Reading only)
564
Operating time carrying-over
times
0
0 to 65535
(reading only)
The numbers of operation time monitor
exceeded 65535h is displayed. (Reading
only)
The above parameters can be set when
Pr.160 Extended function display selection
=
"0".
This parameter allows its setting to be changed during operation in any operation mode even if "0" (initial value) is set in
Pr.77 Parameter write selection
Содержание FR-E700EX
Страница 11: ...VII MEMO ...
Страница 23: ...12 MEMO ...
Страница 288: ...286 MEMO ...
Страница 302: ...300 MEMO ...
Страница 314: ...312 MEMO ...
Страница 315: ...313 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...