Parameter
CC-Link IE Field Network Basic
FR-E700 SC EC/ENE
6 - 357
– Input signals (inverter to master module)
Device No.
Signal
Description
RX0
Forward running
0: Other than forward running (during stop or reverse rotation)
1: Forward running
RX1
Reverse running
0: Other than reverse running (during stop or forward rotation)
1: Reverse running
RX2
Inverter running (terminal RUN function)
앫
A function assigned to terminal RUN is activated.
앫
Signal names are initial values. Using Pr. 190 to Pr. 192, you can change output
signal functions.
RX3
Up to frequency (SU signal)
앫
1: Output frequency has reached the set frequency
앫
The signals are fixed. They cannot be changed using parameters.
RX4
Overload alarm (OL signal)
앫
1: Overload alarm occurrence
앫
The signals are fixed. They cannot be changed using parameters.
RX6
Frequency detection
(terminal FU function)
앫
Functions assigned to terminals FU and ABC activate.
앫
Signal names are initial values. Using Pr.190 to Pr.192, you can change output signal
functions.
RX7
Fault (terminal ABC function)
RX9
Pr. 313 assignment function
(DO0 function)
앫
Functions assigned to Pr.313 to Pr.315 are activated.
앫
Using Pr.190 to Pr.192, you can change output signal functions.
RXA
Pr. 314 assignment function
(DO1 function)
RXB
Pr. 315 assignment function
(DO2 function)
RXC
Monitoring
After "1" is set in the monitor command (RYC), and the monitored value is set in the
remote register Rwr0, 1, 4 to 7, "1" is set in this signal. When "0" is set in the monitor
command (RYC), "0" is set in this signal.
RXD
Frequency setting completion (RAM)
After "1" is set in the frequency setting command (RYD) and the frequency setting
command is written to the inverter RAM, "1" is set in this signal.
When "0" is set in the frequency setting command (RYD), "0" is set in this signal.
RXE
Frequency setting completion
(RAM, E²PROM)
After "1" is set in the frequency setting command (RYE) and the frequency setting
command is written to the inverter RAM and EEPROM, "1" is set in this signal.
When "0" is set in the frequency setting command (RYE), "0" is set in this signal.
RXF
Instruction code execution completion
After "1" is set in the instruction code execution request (RYF) and the processes cor-
responding to the instruction codes (RWw2, 10, 12, 14, 16 and 18) are executed, "1" is
set in this signal.
When "0" is set in the instruction code execution request (RYF), "0" is set in this signal.
RX1A
Error status flag
When an inverter error occurs (protective function is activated), "1" is set in this signal.
RX1B
Remote station ready
When the inverter goes into the ready status upon completion of initial setting after
power-ON or hardware reset, "1" is set in this signal. When an inverter error occurs
(protective function is activated), "0" is set in this signal.
The signal is used as an interlock signal during the write to/read from the master
module.
Tab. 6-157:
The input signals to the master module are indicated. (Output signals from inverter)
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......