Communication operation and setting
Parameter
6 - 256
Setting items and set data
After completion of parameter setting, set the instruction codes and data then start communication
from the computer to allow various types of operation control and monitoring.
No. Item
Read/Write
Instruction
Code
Data Description
Number
of Data
Digits
(Format)
1 Operation Mode
Read
H7B
H0000: Network operation
H0001: External operation
H0002: PU operation
4
(B, E/D)
Write
HFB
4
(A, C/D)
2
M
onit
or
Output frequency/
speed
Read
H6F
H0000 to HFFFF:
Output frequency in 0.01 Hz increments
Speed increments 1/0.001 (when Pr. 37 = 0.01
to 9998)
When "0.01 to 9998" is set in Pr. 37 and "01" in
instruction code HFF, the increments change to
0.001 and the data format is E2.
When "100" is set in Pr. 52, the monitor value is
different depending on whether the inverter is
at a stop or running. (Refer to section 6.11.2.)
4
6
(B, E,
E2/D)
Output current
Read
H70
H0000 to HFFFF:
Output current (hexadecimal) in 0.01 A incre-
ments
4
(B, E/D)
Output voltage
Read
H71
H0000 to HFFFF:
Output voltage (hexadecimal) in 0.1 V
increments
4
(B, E/D)
Special monitor
Read
H72
H0000 to HFFFF:
Monitor data selected in instruction code HF3
4
(B, E/D)
6
(B, E2/D)
Special monitor selec-
tion No.
Read
H73
H01 to H3F:
Monitor selection data
(Refer to Tab. 6-81 on page 6-260.)
2
(B, E1/D)
Write
HF3
2
(A1, C/D)
Fault definition
Read
H74 to H77
H0000 to HFFFF:
(Refer to Tab. 6-82 on page 6-261.)
4
(B, E/D)
3
Run command (extended)
Write
HF9
You can set the control input commands such
as the forward rotation signal (STF) and reverse
rotation signal (STR).
(Refer to page 6-262 for details.)
4
(A, C/D)
Run command
Write
HFA
2
(A1, C/D)
4
Inverter status monitor
(extended)
Read
H79
You can monitor the states of the output sig-
nals such as forward rotation, reverse rotation
and inverter running (RUN).
(Refer to page 6-262 for details.)
4
(B, E/D)
Inverter status monitor
Read
H7A
2
(B, E1/D)
Tab. 6-78:
Setting of the instruction codes and data (1)
Latest alarm
Second fault in past
Fourth fault in past
Sixth fault in past
Eighth fault in past
Third fault in past
Fifth fault in past
Seventh fault in past
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......