42
Profibus PROFILES—PPO Support Specification
PZD
ZSW
BUSY
15
0: Ready status
1: Busy status
If it takes time to perform slave side processing, slave side busy status is announced
since reply to the master will be delayed.
During busy status, other response data are unfixed values. When the slave side is busy,
request from the master is invalid. Therefore, the same request must be sent again.
During busy status, 0 is returned for all Bits except for Bit 15.
HSW
0 to 15 Set frequency (0.01 Hz increments)
HIW
0 to 15 Running frequency (0.01 Hz increments)
ECW
RH
terminal
0
0:RH-OFF
1:RH-ON
Factory-set to high-speed operation command
Pr. 182 can be used to change the signal. *1
RM
terminal
1
0:RM-OFF
1:RM-ON
Factory-set to middle-speed operation command
Pr. 181 can be used to change the signal. *1
RL
terminal
2
0:RL-OFF
1:RL-ON
Factory-set to low-speed operation command
Pr. 180 can be used to change the signal. *1
-
3 to 7
Not used (0 is set)
Command
count
8 to 15 Used by the master to recognize the command response.
*1 Refer to the inverter manual for details of the input terminal function selection (Pr. 180 to Pr. 183).
Name
Bit
Description