Wiring
Control circuit specifications
FR-D700 SC EC
3 - 27
3.4.4
Changing the control logic
FR-D700 SC frequency inverters offer the possibility of choosing between two types of control
logic. Depending on the direction of the flowing current, one distinguishes between:
●
In sink logic, a signal switches on when a current flows from the corresponding signal input
terminal. Terminal SD is common to the contact input signals. Terminal SE is common to
the open collector output signals.
●
In source logic, a signal switches on when a current flows into the corresponding signal input
terminal. Terminal PC is common to the contact input signals. Terminal SE is common to
the open collector output signals.
The input signals are set to source logic (SOURCE) when shipped from the factory. To change
the control logic, the jumper connector above the control circuit terminal block must be moved
to the other position.
(The output signals may be used in either the sink or source logic independently of the jumper
connector position.)
I001029E
Fig. 3-17:
Changing the control logic
Fig. 3-18:
Changing the control logic
I001989E
RUN
RUN
Current flow concerning the input/output
signals when sink logic is selected
Current flow concerning the input/output
signals when source logic is selected
Current
Current
SINK
SOURCE
FR-D700 SC
DC input (sink type),
for example: AX40
DC input (source type),
for example: AX80
Current
Current
+
–
+
FR-D700 SC
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......