Troubleshooting
Causes and corrective actions
FR-D700 SC EC
7 - 5
Operation Panel
Indication
Er3
Name
Calibration error
Description
Analog input bias and gain calibration values are too close.
Corrective action
Check the settings of C3, C4, C6 and C7 (calibration functions). (Refer to section 6.15.3.)
Operation Panel
Indication
Er4
Name
Mode designation error
Description
You attempted to make parameter setting in the External or NET operation mode when
Pr. 77 is not "2".
You attempted to make parameter setting when the command source is not at the
operation panel.
Check point
Check that operation mode is "PU operation mode".
Check the Pr. 77 setting. (Refer to section 6.16.2.)
Check if a parameter unit (FR-PU04/FR-PU07) is connected when Pr. 551 = "9999“
(initial setting).
Check the Pr. 551 setting.
Corrective action
After setting the operation mode to the "PU operation mode", make parameter setting.
(Refer to section 6.16.2.)
After setting "2" in Pr. 72, make parameter setting.
Disconnect the parameter unit (FR-PU04/FR-PU07), and make parameter setting.
After setting Pr. 551 = "4", make parameter setting.
Operation Panel
Indication
Err.
Name
Inverter reset
Description
Executing reset using RES signal, or reset command from communication or PU.
Displays at powering off.
Corrective action
Turn off the RES signal.
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......