Communication operation and settings
Parameter
6 - 236
Modbus registers
●
System environment variable
The communication parameter values are not cleared.
For write, set the data as a control input instruction. For read, data is read as an inverter
operating status.
For write, set data as the operation mode setting. For read, data is read as the operation
mode status.
Register
Definition
Read/Write
Remarks
40002
Inverter reset
Write
Any value can be written
40003
Parameter clear
Write
Set H965A as a written value.
40004
All parameter clear
Write
Set H99AA as a written value.
40006
Parameter clear
Write
Set H5A96 as a written value.
40007
All parameter clear
Write
Set HAA99 as a written value.
40009
Inverter status/control input instruction
Read/write
Refer to Tab. 6-80
40010
Operation mode/inverter setting
Read/write
Refer to Tab. 6-81
40014
Running frequency (RAM value)
Read/write
According to the Pr. 37 setting,
the frequency and selectable
speed are in 1r/min increments.
40015
Running frequency (E²PROM value)
Write
Tab. 6-79:
System environment variable
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......