Communication operation and settings
Parameter
6 - 216
Item
Read/
Write
Instruction
Code
Data Description
Number
of Data
Digits
(Format)
Set frequency (RAM)
Read
H6D
Read set frequency/speed from RAM or
E²PROM.
H0000 to HFFFF: Set frequency in 0.01Hz
increments
Speed increments 1/0.001
(when Pr. 37 = 0.01 to 9998)
When "0.01 to 9998" is set in Pr. 37 and "01"
in instruction code HFF, the increments
change to 0.001 and the data format is E2.
4
(B, E/D)
6
(B, E2/D)
Set frequency (E²PROM)
H6E
Set frequency (RAM)
Write
HED
Write set frequency/speed to RAM or
E²PROM.
H0000 to H9C40 (0 to 400.00Hz):
Frequency increments 0.01Hz
Speed increments 1/0.001
(when Pr. 37 = 0.01 to 9998)
When "0.01 to 9998" is set in Pr. 37 and "01"
in instruction code HFF, the increments
change to 0.001 and the data format is A2.
To change the set frequency consecutively,
write data to the inverter RAM. (instruction
code: HED)
4
(A, C/D)
6
(A2, C/D)
Set frequency
(RAM, E²PROM)
HEE
Inverter reset
Write
HFD
H9696: Resets the inverter.
As the inverter is reset at start of communica-
tion by the computer, the inverter cannot
send reply data back to the computer.
4
(A, C/D)
H9966: Resets the inverter.
When data is sent normally, ACK is returned
to the computer and then the inverter is
reset.
4
(A, D)
Alarm definition all clear
Write
HF4
H9696: Alarm history batch clear
4
(A, C/D)
All parameter clear
Write
HFC
All parameters return to the initial values.
Whether to clear communication parameters
or not can be selected according to data.
(
✔
: Clear, —: Not clear)
When all parameter clear is executed for
H9696 or H9966, communication-related
parameter settings also return to the initial
values. When resuming operation, set these
parameters again.
Executing clear will clear the instruction code
HEC, HF3, and HFF settings. During
password lock, only all parameter clear is
available with H9966 and H55AA.
4
(A, C/D)
Tab. 6-57:
Setting of the instruction codes and data (2)
Clear Type
Data
Communication
parameter
Parameter
clear
H9696
✔
H5A5A
—
All parameter
clear
H9966
✔
H55AA
—
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......