Parameter
Monitor display and monitor output signals
FR-D700 SC EC
6 - 111
6.10.2
Monitor display selection of DU/PU and terminal AM
(Pr. 52, Pr. 158, Pr. 170, Pr. 171, Pr. 268, Pr. 563, Pr. 564, Pr. 891)
The monitor to be displayed on the main screen of the control panel and parameter unit
(FR-PU04/FR-PU07) can be selected.
In addition, signal to be output from the terminal AM (analog voltage output) can be selected.
The above parameters can be set when Pr. 160 = 0.
The above parameters allow its setting to be changed during operation in any operation
mode even if "0" (initial value) is set in Pr. 77 "Parameter write selection".
Pr.
No.
Name
Initial
Value
Setting
Range
Description
Parameters referred to
Refer to
Section
52
DU/PU main display data
selection
0
(output
frequency)
0/5/8–12/
14/20/
23–25/
52–55/61/
62/64/100
Select the monitor to be displayed on the
operation panel and parameter unit.
Refer to Tab. 6-19 for monitor descrip-
tion.
30
70
37
55
56
Regenerative
function selection
Special regenera-
tive brake duty
Speed display
Frequency moni-
toring reference
Current monitor-
ing reference
158
AM terminal function
selection
1
(output
frequency)
1–3/5/
8–12/14/
21/24/
52/53/
61/62
Select the monitor output to terminal AM.
170
Watt-hour meter clear
9999
0
Set "0" to clear the watt-hour meter
monitor.
10
Set the maximum value when monitoring
from communication to 0 to 9999kWh.
9999
Set the maximum value when monitoring
from communication to 0 to 65535kWh.
171
Operation hour meter
clear
9999
0/9999
Set "0" in the parameter to clear the watt-
hour monitor.
Setting "9999" has no effect.
268
Monitor decimal digits
selection
9999
0
Displays as integral value.
1
Displayed in 0.1 increments.
9999
No function
563
Energizing time
carrying-over times
0
0–65535
(reading
only)
The numbers of cumulative energizing
time monitor exceeded 65535h is dis-
played.
Reading only
564
Operating time carrying-
over times
0
0–65535
(reading
only)
The numbers of operation time monitor
exceeded 65535h is displayed.
Reading only
891
Cumulative power moni-
tor digit shifted times
9999
0–4
Set the number of times to shift the
cumulative power monitor digit.
Clamp the monitoring value at maximum.
9999
No shift
Clear the monitor value when it exceeds
the maximum value.
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......