Selection and protection of a motor
Parameter
6 - 74
6.7.3
To exhibit the best performance of the motor performance
(offline auto tuning) (Pr. 71, Pr. 80, Pr. 82 to Pr. 84, Pr. 90, Pr. 96)
The motor performance can be maximized with offline auto tuning.
What is offline auto tuning?
●
When performing general-purpose magnetic flux vector control, the motor can be run with
the optimum operating characteristics by automatically measuring the motor constants
(offline autotuning) even when each motor constants differs, other manufacturer's motor is
used, or the wiring length is long.
The above parameters can be set when Pr. 160 = 0.
Pr.
No.
Name
Initial
Value
Setting Range
Description
Parameters referred to
Refer to
Section
71
Applied motor
0
0/1/3/13/23/40/
43/50/53
By selecting a standard motor or
constant-torque motor, thermal
characteristic and motor con-
stants of each motor are set.
9
71
80
156
178–182
190/
192/197
Electronic ther-
mal O/L relay
Applied motor
Motor capacity
Stall prevention
operation selec-
tion
Input terminal
function selection
Output terminal
function selection
80
Motor capacity
9999
0.1–7.5kW
Applied motor capacity.
9999
V/f control
82
Motor excitation
current
9999
0–500A
Set motor excitation current
(no load current).
9999
Uses the Mitsubishi motor
(SF-JR, SF-HR, SF-JRCA,
SF-HRCA) constants.
83
Rated motor voltage
200V class
200V
0–1000 V
Set the rated motor voltage (V).
400V class
400V
84
Rated motor
frequency
50Hz
10–120Hz
Set the rated motor frequency
(Hz).
90
Motor constant (R1)
9999
0–50
Ω
/9999
Tuning data
(The value measured by offline
auto tuning is automatically set.)
9999: Uses the Mitsubishi motor
(SF-JR, SF-HR, SF-JRCA,
SF-HRCA) constants.
96
Auto tuning setting/
status
0
0
Offline auto tuning is not per-
formed
11
For general-purpose magnetic flux
vector control
Offline auto tuning is performed
without motor running.
(motor constant (R1) only)
21
Offline auto tuning for V/f control
(automatic restart after instanta-
neous power failure (with fre-
quency search))
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......