Basic settings
External operation
FR-D700 SC EC
5 - 37
I001779E
Fig. 5-26:
Operate the inverter by using the analog voltage input
NOTES
When you want to operate in the external operation mode always at powering on or when
you want to save the trouble of input, set "2" (external operation mode) in Pr. 79 "Operation
mode selection" to choose external operation mode always.
Pr. 178 "STF terminal function selection" must be set to "60" (or Pr. 179 "STR terminal func-
tion selection" must be set to "61"). (All are initial values.)
Change the frequency (0Hz) of the minimum value of potentiometer (at 0V) by adjusting the
frequency in calibration parameter C2 "Terminal 2 frequency setting bias frequency". (Refer
to section 6.15.3.)
Power on
→
operation mode check
For the initial setting, the inverter operates in the
external operation mode "EXT" when powering
on. Check that the operation command indication
is "EXT".
If not displayed, press the PU/EXT key
to change to the external "EXT" operation mode.
If the operation mode still does not change, set
Pr. 79 to "0" to change to the external operation
mode. (Refer to section 5.1.6).
Turn the start switch (STF or STR) on.
When the frequency command is not given,
"RUN" flickers fast.
Acceleration
→
constant speed
Turn the potentiometer (frequency setting
potentiometer) clockwise slowly to full.
The frequency value on the indication increases
according to Pr. 7 "Acceleration time" until 50Hz
is displayed.
Deceleration
Turn the potentiometer (frequency setting
potentiometer) counterclockwise slowly to full.
The frequency value on the indication decreases
according to Pr.8 "Deceleration time" and
displays "0.00" (0.00Hz) to stop the motor.
"RUN" flickers fast.
Stop
Turn the start switch (STF or STR) off.
"RUN" turns off.
Operation
Display
Stop
Forward rotation
Reverse rotation
ON
ON
OFF
Flickering
Flickering
Forward rotation
Reverse rotation
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......