background image

FR-D700
INSTALLATION GUIDELINE

FR-D720-008 to 318-NA
FR-D740-012 to 160-NA
FR-D720S-008 to 100-NA
FR-D710W-008 to 042-NA

INVERTER

700

CONTENTS

PRODUCT CHECKING AND PARTS IDENTIFICATION ..........1
OUTLINE DIMENSION DRAWINGS........................................3
WIRING..................................................................................4
PRECAUTIONS FOR USE OF THE INVERTER .....................12
FAILSAFE OF THE SYSTEM WHICH USES THE INVERTER14
PARAMETER LIST ...............................................................15
TROUBLESHOOTING...........................................................19

Thank you for choosing this Mitsubishi Inverter.
Please read through this Installation Guideline and the CD-ROM enclosed to operate this inverter
correctly.
Do not use this product until you have a full knowledge of the equipment, safety information and
instructions.
Please forward this Installation Guideline and the CD-ROM to the end user.

y

Instruction Manual [IB(NA)-0600368ENG]

y

Safety stop function instruction manual [BCN-A211508-000]

These manuals are required if you are going to utilize functions and
performance.

1
2
3
4
5
6
7

Содержание FR-D710W-008

Страница 1: ...SHOOTING 19 Thank you for choosing this Mitsubishi Inverter Please read through this Installation Guideline and the CD ROM enclosed to operate this inverter correctly Do not use this product until you have a full knowledge of the equipment safety information and instructions Please forward this Installation Guideline and the CD ROM to the end user y Instruction Manual IB NA 0600368ENG y Safety sto...

Страница 2: ...g Otherwise you may get an electric shock z Do not change the cooling fan while power is ON It is dangerous to change the cooling fan while power is ON z Do not touch the printed circuit board or handle the cables with wet hands Otherwise you may get an electric shock z When measuring the main circuit capacitor capacity the DC voltage is applied to the motor for 1s at powering OFF Never touch the ...

Страница 3: ...or and generator z When driving a 400V class motor by the inverter the motor must be an insulation enhanced motor or measures must be taken to suppress surge voltage Surge voltage attributable to the wiring constants may occur at the motor terminals deteriorating the insulation of the motor z When parameter clear or all parameter clear is performed the required parameters must be set again before ...

Страница 4: ...ature exceeds 40 C 104 F clearances between the inverters should be 1cm 0 39inches or more 5cm 1 96inches or more for the FR D720 238 and FR D740 120 or higher y Install the inverter vertically FR D740 036 NA Symbol Voltage class D740 Three phase 400V class Rating plate Inverter model Input rating Output rating Serial number FR D740 036 NA Inverter model Rating plate Represents the rated current I...

Страница 5: ... 4 F to 149 F Temperature applicable for a short time e g in transit Ambience Indoors free from corrosive gas flammable gas oil mist dust and dirt Altitude vibration Maximum 1000m 3280 80feet above sea level for standard operation After that derate by 3 for every extra 500m 1640 40feet up to 2500m 8202feet 91 5 9m s2 or less at 10 to 55Hz directions of X Y Z axes Note y Install the inverter on a s...

Страница 6: ...2 FR D740 036 135 5 5 34 FR D740 050 155 5 6 12 FR D740 080 165 5 6 52 FR D740 120 220 8 66 208 8 19 150 5 91 138 5 43 155 6 10 FR D740 160 Inverter Model W W1 H H1 D C FR D720S 008 68 2 68 56 2 20 128 5 04 118 4 65 80 5 3 17 5 0 20 FR D720S 014 FR D720S 025 142 5 5 61 FR D720S 042 162 5 6 40 FR D720S 070 108 4 25 96 3 78 155 5 6 12 FR D720S 100 140 5 51 128 5 04 150 5 91 138 5 43 145 5 71 Inverte...

Страница 7: ...nnector 1 DC reactor FR HEL When connecting a DC reactor remove the jumper across P1 P Single phase 100V power input model is not compatible with DC reactor Control circuit terminal Main circuit terminal Sink logic Jumper 1 6 8 7 2 3 5 The function of these terminals can be changed to the reset signal etc with the input terminal assignment Pr 178 to Pr 182 Multi speed selection Terminal functions ...

Страница 8: ...12 to 080 FR D740 120 160 FR D720S 012 to 080 FR D720S 120 160 Screw size M3 5 Motor Power supply N P PR IM R L1 S L2 T L3 Jumper Screw size M3 5 Screw size M4 Motor Power supply N P PR IM R L1 S L2 T L3 Jumper Screw size M4 Power supply Motor IM Screw size M5 Screw size M5 Jumper N P PR R L1S L2 T L3 N P PR R L1 S L2 T L3 Screw size M4 Motor Power supply IM Jumper Screw size M4 N P PR R L1 S L2 T...

Страница 9: ...ect the power cable to the U V W of the inverter Doing so will damage the inverter y Connect the motor to U V W Turning ON the forward rotation switch signal at this time rotates the motor counterclockwise when viewed from the load shaft N P PR R L1 S L2 Screw size M3 5 Motor Power supply IM Screw size M3 5 N P PR R L1 S L2 Screw size M4 Motor Power supply IM Screw size M4 ...

Страница 10: ...l screw size indicates the size of terminal screw for R L1 S L2 U V W PR P N P1 and a screw for earthing grounding Applicable Inverter Model Terminal Screw Size 4 Tightening Torque N m Crimping Terminal Cable Size HIV Cables etc mm2 1 AWG 2 PVC Cables etc mm2 3 R L1 S L2 T L3 U V W R L1 S L2 T L3 U V W Earthing ground cable R L1 S L2 T L3 U V W R L1 S L2 T L3 U V W Earthing ground cable FR D720 00...

Страница 11: ...uction in the low speed range NOTE y Tighten the terminal screw to the specified torque A screw that has been tighten too loosely can cause a short circuit or malfunction A screw that has been tighten too tightly can cause a short circuit or malfunction due to the unit breakage y Use crimping terminals with insulation sleeve to wire the power supply and motor 3 wire resistance mΩ m wiring distance...

Страница 12: ... higher FR D720S 070 or higher FR D740 080 or higher Wiring Length 50m 164 04feet or less 50m 164 04feet to 100m 328 08feet Exceeding 100m 323 08feet Carrier frequency 14 5kHz or less 8kHz or less 2kHz or less NOTE y Especially for long distance wiring the inverter may be affected by a charging current caused by the stray capacitances of the wiring leading to a malfunction of the overcurrent prote...

Страница 13: ...ade terminal of which the crimping is inappropriate or the face is damaged Blade terminals available on the market as of January 2010 zPhoenix Contact Co Ltd 1 A blade terminal with an insulation sleeve compatible with MTW wire which has a thick wire insulation 2 Applicable for terminal ABC zNICHIFU Co Ltd Wire stripping length Wire Size mm2 Blade Terminal Model Crimping Tool Name With Insulation ...

Страница 14: ...out a blade terminal push an open close button all the way down with a flathead screw driver and insert the wire Note y When using a stranded wire without a blade terminal twist enough to avoid short circuit with a nearby terminals or wires y Place the flathead screwdriver vertical to the open close button In case the blade tip slips it may cause damage of inverter or injury Pull the wire with pus...

Страница 15: ...power factor correction capacitor surge suppressor or capacitor type filter on the inverter output side This will cause the inverter to trip or the capacitor and surge suppressor to be damaged If any of the above devices are connected immediately remove them When using capacitor type filter FR BIF for a single phase power input model make sure of secure insulation of T phase and connect to the inp...

Страница 16: ...r is turned ON while the inverter is operating overcurrent protection of the inverter and such will activate When MC is provided for switching to the commercial power supply for example switch it ON OFF after the inverter and motor have stopped 17 Countermeasures against inverter generated EMI If electromagnetic noise generated from the inverter is causing frequency setting signal to fluctuate and...

Страница 17: ...em 1 Start signal and actual operation check Check the motor running and motor current while the start signal is input to the inverter by comparing the start signal to the inverter and detected speed of the speed detector or detected current of the current detector Note that the motor current runs as the motor is running for the period until the motor stops since the inverter starts decelerating e...

Страница 18: ...120Hz 19 Base frequency voltage 0 to 1000V 8888 9999 9999 20 Acceleration deceleration reference frequency 1 to 400Hz 60Hz 22 Stall prevention operation level 0 to 200 150 23 Stall prevention operation level compensation factor at double speed 0 to 200 9999 9999 24 Multi speed setting speed 4 0 to 400Hz 9999 9999 25 Multi speed setting speed 5 0 to 400Hz 9999 9999 26 Multi speed setting speed 6 0 ...

Страница 19: ...0 to 400Hz 60Hz 126 Terminal 4 frequency setting gain frequency 0 to 400Hz 60Hz 127 PID control automatic switchover frequency 0 to 400Hz 9999 9999 128 PID action selection 0 20 21 40 to 43 0 Pr Name Setting Range Initial Value 129 PID proportional band 0 1 to 1000 9999 100 130 PID integral time 0 1 to 3600s 9999 1s 131 PID upper limit 0 to 100 9999 9999 132 PID lower limit 0 to 100 9999 9999 133 ...

Страница 20: ...ecimal digits selection 0 1 9999 9999 269 Parameter for manufacturer setting Do not set 295 Magnitude of frequency change setting 0 0 01 0 10 1 00 10 00 0 296 Password lock level 1 to 6 101 to 106 9999 9999 297 Password lock unlock 1000 to 9998 0 to 5 9999 9999 298 Frequency search gain 0 to 32767 9999 9999 299 Rotation direction detection selection at restarting 0 1 9999 0 338 Communication opera...

Страница 21: ... Parameter clear 0 1 0 ALLC All parameter clear 0 1 0 Er CL Faults history clear 0 1 0 Pr CH Initial value change list Pr Name Setting Range Initial Value 1 Differ according to capacities 6 FR D720 042 or lower FR D740 022 or lower FR D720S 042 or lower FR D710W 042 or lower 4 FR D720 070 to 165 FR D740 036 to 080 FR D720S 070 and 100 3 FR D720 238 and 318 FR D740 120 and 160 2 Differ according to...

Страница 22: ... trip 2 Warning The inverter does not trip even when a warning is displayed However failure to take appropriate measures will lead to a fault 3 Alarm The inverter does not trip You can also output an alarm signal by making parameter setting 4 Fault When a fault occurs the inverter trips and a fault signal is output 7 1 Reset method of protective function 1 Resetting the inverter The inverter can b...

Страница 23: ...leration or stop E OV1 Regenerative overvoltage trip during acceleration E OV2 Regenerative overvoltage trip during constant speed E OV3 Regenerative overvoltage trip during deceleration or stop E THT Inverter overload trip electronic thermal O L relay function E THM Motor overload trip electronic thermal O L relay function E FIN Heatsink overheat to Fault E ILF Input phase loss E OLT Stall preven...

Страница 24: ...ective We declare that this inverter when equipped with the EMC Directive compliant EMC filter conforms with the EMC Directive and affix the CE marking on the inverter except the single phase 100V power supply model y EMC Directive 2004 108 EC y Standard s EN61800 3 2004 Second environment PDS Category C3 Note First environment Environment including residential buildings Includes building directly...

Страница 25: ...I usable regardless of the earth ground condition of the power supply overvoltage category III usable with the earthed neutral system power supply 400V class only specified in IEC664 yTo use the inverter under the conditions of pollution degree 3 install it in the enclosure of IP54 or higher yTo use the inverter outside of an enclosure in the environment of pollution degree 2 fix a fan cover with ...

Страница 26: ...tor and stops the output The operation characteristic is shown on the left When using the Mitsubishi constant torque motor 1 Set 1 or any of 13 50 53 in Pr 71 This provides a 100 continuous torque characteristic in the low speed range 2 Set the rated current of the motor in Pr 9 1 When 50 of the inverter rated output current current value is set in Pr 9 2 The value denotes the percentage to the in...

Страница 27: ...ropriate rating or Listed UL 489 Molded Case Circuit Breaker MCCB must be employed Refer to page 23 4 Short circuit ratings 100V class Suitable For Use in A Circuit Capable of Delivering Not More Than 100 kA rms Symmetrical Amperes 132 V Maximum 200V class Suitable For Use in A Circuit Capable of Delivering Not More Than 100 kA rms Symmetrical Amperes 264 V Maximum 400V class Suitable For Use in A...

Страница 28: ...ontrol you are strongly advised to install safety devices to prevent serious accidents when it is used in facilities where breakdowns of the product are likely to cause a serious accident Please do not use this product for loads other than three phase induction motors Print Date Manual Number Revision Sep 2008 IB 0600367ENG A First edition Oct 2008 IB 0600367ENG B y FR D710W 008 to 042 NA Jun 2009...

Страница 29: ...ing this CD ROM on Windows OS Operating environment The following system is required to read instruction manuals contained in this CD ROM Operating method of this CD ROM How to read instruction manuals Step 1 Start Windows and place this CD ROM in the CD ROM drive Step 2 FR D700 series documents PDF automatically opens Step 3 Click a manual you want to read in the INSTRUCTION MANUAL list Step 4 PD...

Страница 30: ...8 0 2 55 088 41 e mall UTECO A B E E GREECE 5 Mavrogenous Str GR 18542 Piraeus Phone 30 0 1 42 10 050 Fax 30 0 1 42 12 033 e mall uteco uteco gr MITSUBISHI ELECTRIC IRELAND EUROPE B V Irish Branch Westgate Business Park Ballymount IRL Dublin 24 Phone 353 0 1 419 88 00 Fax 353 0 1 419 88 90 e mail sales info meuk mee com ALFATRADE LTD MALTA 99 Paola Hill Paola PLA 08 Phone 356 697816 Fax 356 697817...

Отзывы: