Causes and corrective actions
Operation panel
indication
E.5
FR-PU04
FR-PU07
Fault 5
E.CPU
CPU Fault
Name
CPU fault
Description
Stops the inverter output if the communication fault of the built-in CPU occurs.
Check point
Check for devices producing excess electrical noises around the inverter.
Corrective action
Take measures against noises if there are devices producing excess electrical noises around the inverter.
Please contact your sales representative.
Operation panel
indication
E.CDO
FR-PU04
Fault 14
FR-PU07
OC detect level
Name
Output current detection value exceeded
Description
This function is activated when the output current exceeds the
Pr. 150 Output current detection level
setting.
Check point
Check the settings of
Pr. 150 Output current detection level
,
Pr. 151 Output current detection signal delay time
,
Pr. 166 Output
current detection signal retention time
,
Pr. 167 Output current detection operation selection
)
Operation panel
indication
E.IOH
FR-PU04
Fault 14
FR-PU07
Inrush overheat
Name
Inrush current limit circuit fault
Description
This function is activated when the resistor of the inrush current limit circuit overheats. The inrush current limit circuit fault
Check point
Check that frequent power ON/OFF is not repeated.
Corrective action
Configure a circuit where frequent power ON/OFF is not repeated.
If the problem still persists after taking the above measure, please contact your sales representative.
Operation panel
indication
E.AIE
FR-PU04
Fault 14
FR-PU07
Analog in error
Name
Analog input fault
Description
Appears if voltage(current) is input to terminal 4 when the setting in
Pr.267 Terminal 4 input selection
and the setting of
voltage/current input switch are different.
Check point
Check the setting of
Pr. 267 Terminal 4 input selection
and voltage/current input switch.
Corrective action
Either give a frequency command by current input or set
Pr. 267 Terminal 4 input selection
, and voltage/current input
switch to voltage input.
Operation panel
indication
E.SAF
FR-PU04
Fault 14
FR-PU07
Fault
E.SAF
Name
Safety circuit fault
Description
Appears when safety circuit is malfunctioning.
Appears when one of the lines between S1 and SC, or between S2 and SC is opened.
Check point
Check if the shorting wire between S1 and SC or between S2 and SC is disconnected when not using the safety
stop function.
Check that the safety relay module or the connection has no fault when using the safety stop function.
Corrective action
When not using the safety stop function, short across terminals S1 and SC and across S2 and SC with shorting
wire.
When using the safety stop function, check that wiring of terminal S1, S2 and SC is correct and the safety stop
input signal from safety relay module is operating properly.
Refer to the Safety stop function instruction manual (BCN-
A211508-000)
for causes and countermeasures.
(Please contact your sales representative for the manual.)
NOTE
If protective functions of E.ILF, E.AIE, E.IOH, E.PTC, E.CDO, E.SAF are activated when using the FR-PU04, "Fault 14"
is displayed.
Also when the faults history is checked on the FR-PU04, the display is "E.14".
If faults other than the above appear, contact your sales representative.
Содержание FR-D710W-0.1K
Страница 45: ...36 MEMO ...
Страница 61: ...52 MEMO ...
Страница 254: ...252 MEMO ...
Страница 296: ...294 MEMO ...
Страница 297: ...295 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 308: ...4 4 BCN C22005 652 MEMO bcnc22005652 fm 4 ページ 2013年12月26日 木曜日 午後12時58分 ...
Страница 312: ...4 4 BCN C22005 689 MEMO ...