(H) Protective function parameter
96
5.3
(H) Protective function parameter
5.3.1
Varying the activation level of the undervoltage
protective function
5.3.2
Initiating a protective function
• To initiate a fault (protective function), set the assigned number of the protective function you want to initiate in
Pr.997
.
• The value set in
Pr.997
is not stored in EEPROM.
• When the protective function is activated, the inverter output is shut off and the converter unit displays a fault to output a
Fault (ALM, ALM2) signal.
• The latest fault in the fault history is displayed while the fault initiation function is in operation. After a reset, the fault history
goes back to the previous status. (The protective function generated by the fault is not saved in the fault history.)
• Perform converter reset to cancel the protective function.
• For the selectable parameter by
Pr.997
and the corresponding protective functions, refer to
NOTE
• If a protective function is already operating, no protective function cannot be initiated by
Pr.997
.
• If a fault occurs after a protective function has been activated, the protective function indication does not change. The fault is
not saved in the fault history either.
Purpose
Parameter to set
Refer to
page
To vary the operating level of the
undervoltage protective function
Undervoltage level
P.H102
Pr.598
To initiate an inverter protective
function
Fault initiation
P.H103
Pr.997
To disable the I/O phase loss
protective function
Input phase loss
protection selection
P.H201
Pr.872
To operate without activating
protective functions in case of
emergency
Emergency drive
P.H301, P.H320,
P.H322, P.H324
Pr.67, Pr.514
Pr.515, Pr.523
If the undervoltage protection (E.UVT) is activated due to unstable voltage in the power supply, the undervoltage level
(DC bus voltage value) can be changed.
Pr.
Name
Initial
value
Setting range
Description
598
H102
Undervoltage level
9999
350 to 430 VDC
Set the DC voltage value at which E.UVT occurs.
9999
E.UVT occurs at 430 VDC.
A fault (protective function) is initiated by setting the parameter.
This function is useful to check how the system operates at activation of a protective function.
Pr.
Name
Initial
value
Setting
range
Description
997
H103
Fault initiation
9999
16 to 253
The setting range is same with the one for fault data codes of
the converter unit (which can be read through
communication).
Written data is not stored in EEPROM.
9999
The read value is always "9999".
With this setting, the protective function is not activated.