background image

Operation panel

BASIC OPERATION

77

4

4.1.4

Changing the parameter setting value

NOTE

 •

 is displayed... Why?

appears... Write disable error

For the details, refer to 

page 142

.

Changing example

Change 

Pr.774 Operation panel monitor selection 1

.

Operation

1.

Screen at power-ON

The monitor display appears.

2.

Parameter setting mode

Press 

 to choose the parameter setting mode. (The parameter number read previously appears.)

3.

Selecting the parameter number

Turn  

until 

 

(Pr.774)

 appears. Press 

 to read the present set value. "

" (initial value) 

appears.

4.

Changing the setting value

Turn 

 to change the set value to "

". Press 

 to enter the setting. "

" and "

" blink alternately.

Turn 

 to read another parameter.

Press 

 to show the setting again.

Press 

 twice to show the next parameter.

Press 

 twice to return to the monitor display of the converter output voltage.

Содержание FR-CC2-P

Страница 1: ...ONS FOR USE OF THE CONVERTER UNIT 3 BASIC OPERATION 4 PARAMETER 5 PROTECTIVE FUNCTIONS 6 PRECAUTIONS FOR MAINTE NANCE AND INSPECTION 7 SPECIFICATIONS 8 CC2 FR CC2 P CONVERTER UNIT FOR PARALLEL OPERATION INSTRUCTION MANUAL FR CC2 H400K to H560K P Converter Unit ...

Страница 2: ...hed grounded power supply for converter unit in compliance with EN standard must be used Any person who is involved in wiring or inspection of this equipment shall be fully competent to do the work The converter unit must be installed before wiring Otherwise you may get an electric shock or be injured Do not touch the setting dial or keys with wet hands Doing so may cause an electric shock Do not ...

Страница 3: ... or All parameter clear is performed the parameters must be set again as required before the operation is started Perform an inspection and test operation of this product if it has been stored for a long period of time Static electricity in your body must be discharged before you touch the product To maintain the security confidentiality integrity and availability of the Converter unit drive unit ...

Страница 4: ...wiring of the power supply and the inverter 35 2 5 3 Applicable cables 37 2 5 4 Earthing grounding precautions 38 2 6 Main circuit terminals for 12 phase rectification 39 2 6 1 Details on the main circuit terminals 39 2 6 2 Connection diagram with 12 phase rectifier power transformer 39 2 6 3 12 phase rectifier power transformer 39 2 6 4 Wiring method 40 2 6 5 Recommended cables 41 2 6 6 Earthing ...

Страница 5: ...ing the converter unit status 78 4 2 1 Monitoring of converter output voltage and input current 78 4 2 2 First monitored item 78 5 PARAMETER 79 5 1 Parameter list 80 5 1 1 Parameter list by parameter number 80 5 1 2 Parameter display by function group 83 5 1 3 Parameter list by function group 84 5 2 E Environment setting parameters 86 5 2 1 Simple clock function 87 5 2 2 Reset selection disconnect...

Страница 6: ...tions of RS 485 communication 118 5 7 4 Mitsubishi inverter protocol computer link communication 119 5 8 Parameter clear all parameter clear 131 5 9 Copying and verifying parameters 132 5 9 1 Parameter copy 132 5 9 2 Parameter verification 134 5 10 Checking parameters changed from their initial values Initial value change list 135 6 PROTECTIVE FUNCTIONS 137 6 1 Converter unit fault and alarm indic...

Страница 7: ... converter output voltage across terminals P and N 162 7 2 6 Insulation resistance test using megger 163 7 2 7 Withstand voltage test 163 8 SPECIFICATIONS 165 8 1 Converter unit rating 166 8 2 Common specifications 166 8 3 Outline dimension drawings 167 8 3 1 Converter unit outline dimension drawings 167 APPENDIX 169 Appendix 1 Instruction code list 170 Appendix 2 Instructions for compliance with ...

Страница 8: ... to function Trademarks Microsoft and Visual C are registered trademarks of Microsoft Corporation in the United States and other countries Other company and product names herein are the trademarks and registered trademarks of their respective owners Notes on descriptions in this Instruction Manual Connection diagrams in this Instruction Manual suppose that the control logic of the input terminal i...

Страница 9: ...ts of one symbol two characters indicating the production year and month and six characters indicating the control number The last digit of the production year is indicated as the Year and the Month is indicated by 1 to 9 X October Y November or Z December Symbol Year Month Control number SERIAL Rating plate Input rating Output rating SERIAL Converter unit model Country of origin F R C C 2 H 400K ...

Страница 10: ...ontrol circuit 43 g EMC filter ON OFF connector Turns ON OFF the EMC filter 65 h Main circuit conductor Connects cables for the main circuit 35 i Charge lamp Stays ON while the power is supplied to the main circuit 35 j Alarm lamp Turns ON when the protective function of the converter is activated 35 k Power lamp Stays ON while the power is supplied to the control circuit R1 L11 S1 L21 35 l Front ...

Страница 11: ...s Manuals related to the FR CC2 P converter unit are shown in the following table Name Manual number FR A802 P Instruction Manual Hardware IB 0600651ENG Parallel Operation Function Manual IB 0600654ENG FR A800 Instruction Manual Detailed IB 0600503ENG ...

Страница 12: ...ing the equipment 2 1 Peripheral devices 12 2 2 Removal and reinstallation of the front cover 18 2 3 Installation of the converter unit and enclosure design 20 2 4 Terminal connection diagrams 27 2 5 Main circuit terminals 6 phase rectification 35 2 7 Control circuit 43 2 8 Communication connectors and terminals 53 2 9 Setting parameters for parallel operation 56 ...

Страница 13: ... a Inverter FR A802 P a Inverter FR A802 P g Noise filter Earth Ground Earth Ground Earth Ground Earth Ground g Noise filter c Three phase AC power supply R L1 S L2 T L3 N P N P U V W Install these options as required R L1 S L2 T L3 N P N P U V W One circuit breaker and one magnetic contactor per converter unit One circuit breaker and one magnetic contactor in total in a system To the master conve...

Страница 14: ...ll inverters also must be the same Symbol Name Overview Refer to page a Inverter FR A802 P The life of the inverter and the converter unit is influenced by the surrounding air temperature The surrounding air temperature should be as low as possible within the permissible range This must be noted especially when the inverter is installed in an enclosure Incorrect wiring may lead to damage of the in...

Страница 15: ...00K 1800 A 1600 A rated product H450K 2100 A 1800 A rated product H500K 2200 A 1900 A rated product H560K 2400 A 2100 A rated product Select an MCCB according to the power supply capacity Install one MCCB per converter unit For the use in the United States or Canada refer to page 176 to select an appropriate fuse or molded case circuit breaker MCCB The magnetic contactor is selected based on the A...

Страница 16: ...er MCCB The magnetic contactor is selected based on the AC 1 class The electrical durability of magnetic contactor is 500 000 times When the magnetic contactor is used for emergency stops during motor driving the electrical durability is 25 times If using an MC for emergency stop during driving the motor select an MC regarding the converter unit input side current as JEM1038 AC 3 class rated curre...

Страница 17: ...is 500 000 times When the magnetic contactor is used for emergency stops during motor driving the electrical durability is 25 times When using an MC for emergency stop during driving the motor select the MC with JEM 1038 AC 3 class rated current for the converter unit input current When providing an MC on the inverter output side for switching to commercial power supply during general purpose moto...

Страница 18: ... the breaker on the converter unit s input side trips check for the wiring fault short circuit damage to internal parts of the inverter or the converter unit etc The cause of the trip must be identified and removed before turning ON the power of the breaker When the inverter is operated while the power distribution control equipment connected between the delta wiring of the transformer and termina...

Страница 19: ...e front cover lower side removed wiring of the main circuit terminals can be performed Loosen the two fixing screws on the accessory cover These screws cannot be removed Push the upper edge of the accessory cover and pull the accessory cover to remove To install the inverter operation panel align its connector on the back with the PU connector of the inverter and insert the operation panel After c...

Страница 20: ...per side removed wiring of the control circuit or the RS 485 terminals can be performed Reinstallation of the front cover a Insert the upper hooks of the front cover upper side into the sockets of the converter unit Insert the upper hooks of the front cover upper side into the sockets of the converter unit b Tighten the mounting screw at the lower part of the front cover upper side c Fasten the fr...

Страница 21: ...rvice lives of the semiconductors parts capacitors and others Take the following measures to keep the surrounding air temperature of the converter unit within the specified range a Measures against high temperature Use a forced ventilation system or similar cooling system Refer to page 22 Install the enclosure in an air conditioned electric chamber Block direct sunlight Provide a shield or similar...

Страница 22: ... higher than the outside air pressure Corrosive gas salt damage If the converter unit is exposed to corrosive gas or to salt near a beach the printed board patterns and parts will corrode or the relays and switches will result in poor contact In such places take the above mentioned measures Explosive flammable gases As the converter unit is non explosion proof it must be contained in an explosion ...

Страница 23: ...r or cooler heat pipe cooler etc Cooling system Enclosure structure Comment Natural cooling Natural ventilation enclosed ventilated type This system is low in cost and generally used but the enclosure size increases as the converter unit capacity increases This system is for relatively small capacities Natural ventilation totally enclosed type Being a totally enclosed type this system is the most ...

Страница 24: ...nit and the other devices or enclosure surface The clearance below the converter unit is required as a wiring space and the clearance above the converter unit is required as a heat dissipation space For replacing the cooling fan 30 cm or more of space is necessary in front of the converter unit Refer to page 159 for fan replacement Installation orientation of the converter unit Install the convert...

Страница 25: ...e the surrounding air temperature of the inverter and the converter unit higher than the permissible value by providing ventilation and increasing the enclosure size Arrangement of multiple inverters and converter units Heat generated in the converter unit is blown up from the bottom of the unit as warm air by the cooling fan When installing a ventilation fan for that heat determine the place of v...

Страница 26: ...nverter unit to an enclosure the heat generated in the enclosure can be greatly reduced by protruding the heat sink of the converter unit When installing the converter unit in a compact enclosure etc this installation method is recommended Panel cutting Cut the panel of the enclosure Unit mm 580 200 200 15 15 1550 1520 6 M10 screw Hole ...

Страница 27: ...t etc into the converter unit and cooling fan section One installation frame is attached to each of the upper and lower parts of the converter unit Remove the rear side installation frame on the top and bottom sides of the converter unit as shown on the right Upper installation frame Lower installation frame Converter unit 185 mm Inside the enclosure Enclosure Exhausted air Installation frame Dime...

Страница 28: ...ut side After wiring wire offcuts must not be left in the inverter or the converter unit Wire offcuts can cause an alarm failure or malfunction Always keep the inverter and the converter unit clean When drilling mounting holes in an enclosure etc take caution not to allow chips and other foreign matter to enter the inverter or the converter unit Three phase AC power supply MCCB Jumper R L1 S L2 T ...

Страница 29: ...main circuit cables at the output side After wiring wire offcuts must not be left in the inverter or the converter unit Wire offcuts can cause an alarm failure or malfunction Always keep the inverter and the converter unit clean When drilling mounting holes in an enclosure etc take caution not to allow chips and other foreign matter to enter the inverter or the converter unit Three phase AC power ...

Страница 30: ...cally once the RS 485 terminals have been wired and Pr 1001 has been set on all converters NOTE Set up the slave converter unit first before the master converter unit by the Pr 1001 setting and the converter unit reset Otherwise an error may occur in communication between the converter units For inverters that are connected in parallel ensure that the three phase wiring between each motor and inve...

Страница 31: ...r FR CC2 P slave FR A802 P slave P N P N MRS X10 Single wound motor RES SD RDB RDA IPF RSO FAN SE R L1 S L2 T L3 U V W R1 L11 S1 L21 S1 L21 R1 L11 TXD1 TXD2 TXD1 TXD2 RXD1 RXD2 RXD2 RXD1 GND SG GND SG M Three phase AC power supply FR POL FR POL R L1 S L2 T L3 S1 L21 R1 L11 P N RDB RDA IPF RSO FAN SE TXD1 TXD2 TXD1 TXD2 RXD1 RXD2 RXD2 RXD1 GND SG GND SG P N R1 L11 S1 L21 TXD1 TXD2 TXD1 TXD2 RXD1 RX...

Страница 32: ...ls U V and W on the output sides of the master station and the slave station FR CC2 P master FR A802 P master FR CC2 P slave FR A802 P slave P N P N MRS X10 Multi wound motor RES SD RDB RDA IPF RSO FAN SE R L1 S L2 T L3 U V W R1 L11 S1 L21 S1 L21 R1 L11 TXD1 TXD2 TXD1 TXD2 RXD1 RXD2 RXD2 RXD1 GND SG GND SG M Three phase AC power supply R L1 S L2 T L3 S1 L21 R1 L11 P N RDB RDA IPF RSO FAN SE TXD1 T...

Страница 33: ...the RS 485 terminals have been wired and Pr 1001 has been set on all converters NOTE It is not important which order steps 2 and 3 are performed in Set up the slave converter unit first before the master converter unit by the Pr 1001 setting and the converter unit reset Otherwise an error may occur in communication between the converter units For inverters that are connected in parallel ensure tha...

Страница 34: ...L11 S1 L21 S1 L21 P N R L1 S L2 T L3 S1 L21 R1 L11 R1 L11 P N U V W R1 L11 S1 L21 GND SG TXD1 TXD2 TXD1 TXD2 RXD1 RXD2 RXD2 RXD1 GND SG GND SG TXD1 TXD2 TXD1 TXD2 RXD1 RXD2 RXD2 RXD1 GND SG GND SG TXD1 TXD2 TXD1 TXD2 RXD1 RXD2 RXD2 RXD1 GND SG GND SG FR CC2 P slave 2 FR A802 P slave 2 P N R L1 S L2 T L3 S1 L21 R1 L11 P N U V W R1 L11 S1 L21 TXD1 TXD2 TXD1 TXD2 RXD1 RXD2 RXD2 RXD1 GND SG GND SG TXD...

Страница 35: ...he terminal used for the X10 signal input set 10 in any of Pr 178 to Pr 189 Input terminal function selection to assign the function To use the RDA signal of the converter unit select the NC contact input specification for the input logic of the MRS signal or X10 signal of the inverter To use the RDB signal of the converter unit select the NO contact input specification for the input logic of the ...

Страница 36: ...ower supply terminals R L1 and S L2 To retain the fault display and fault output remove the jumpers across terminals R L1 and R1 L11 and across S L2 and S1 L21 and supply external power to these terminals When using a separate power supply connected to terminals R1 L11 and S1 L21 the required power capacity is 80 VA 50 P N Inverter connection Wire the terminals as shown in the terminal connection ...

Страница 37: ... tighten a nut from the right side of the conductor When wiring two wires place wires on both sides of the conductor Refer to the drawing below For wiring use bolts nuts provided with the converter unit When wiring cables to the main circuit conductor R L1 S L2 T L3 of the converter unit use the bolts nuts for main circuit wiring which are provided on the front side of the conductor Connect the ca...

Страница 38: ...closure Selection example for use mainly in Europe Screws for terminals R L1 S L2 T L3 P N and the screw for earthing grounding The size of the earthing grounding screw is indicated in parentheses The line voltage drop can be calculated by the following formula Line voltage drop V Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop torque...

Страница 39: ...arate earth ground system I is not feasible Do not make inadequate common single point earth ground connection III A leakage current containing many high frequency components flows into the earthing grounding cables of the converter unit Because of this the converter unit must be earthed grounded separately from EMI sensitive devices In a high building it may be effective to use the EMI prevention...

Страница 40: ... Refer to page R L1 S L2 T L3 AC power input Connect these terminals to the output terminals in the wye connection of a 12 phase transformer 3 winding transformer 40 R2 L12 S2 L22 T2 L32 AC power input Connect these terminals to the output terminals in the delta connection of a 12 phase transformer 3 winding transformer 40 R1 L11 S1 L21 Power supply for the control circuit Connected to the AC powe...

Страница 41: ...L2 and T L3 of the converter unit Likewise connect the output terminals in the delta connection of the transformer with terminals R2 L12 S2 L22 and T2 L32 of the converter unit Use the bolts and nuts removed earlier for these connections NOTE Make sure to connect the power cables to the right terminals one set to terminals R L1 S L2 and T L3 and the other set to terminals R2 L12 S2 L22 and T2 L32 ...

Страница 42: ...erature of 90 C XLPE cable It assumes a surrounding air temperature of 40 C or lower and in enclosure wiring Selection example mainly for use in Europe It is applied to the screws for terminals R L1 S L2 T L3 P and N and a screw for earthing grounding Screw size for earthing grounding is indicated in parentheses The crimp terminals are the same for R2 L12 S2 L22 and T2 L32 The line voltage drop ca...

Страница 43: ...ng grounding for the converter unit Establishing adequate common single point earth ground system II shown in the following figure is allowed only in cases where the separate earth ground system I is not feasible Do not make inadequate common single point earth ground connection III A leakage current containing many high frequency components flows into the earthing grounding cables of the converte...

Страница 44: ... operation E OHT RDI Contact input No function is assigned in the initial setting The function can be assigned by setting Pr 178 SD Contact input common sink Common terminal for contact input terminal sink logic External transistor common source Connect this terminal to the power supply common terminal of a transistor output open collector output device such as a programmable controller in the sou...

Страница 45: ... Switched to LOW when the converter is reset RES ON Assign the signal to terminal RES of the inverter The inverter is reset when it is connected with the RSO status LOW IPF Instantaneous power failure Switched to LOW when an instantaneous power failure is detected FAN Cooling fan fault Switched to LOW when a cooling fan fault occurs SE Open collector output common Common terminal for terminals RDA...

Страница 46: ...jumper connector to the connector pin of the desired control logic The jumper connector is in the sink logic SINK when shipped from the factory The output signals may be used in either the sink or source logic independently of the jumper connector position NOTE Make sure that the jumper connector is installed correctly Never change the control logic while power is ON Jumper connector Jumper connec...

Страница 47: ...verter unit due to undesirable currents Source logic Use terminal SD as a common terminal and perform wiring as shown below Do not connect terminal PC of the converter unit with terminal 24V of the external power supply When using terminals PC SD as a 24 VDC power supply do not install an external power supply in parallel with the converter unit Doing so may cause a malfunction in the converter un...

Страница 48: ...f the sleeve Check the condition of the crimp terminals after crimping Do not use the crimp terminals of which the crimping is inappropriate or the face is damaged Crimp terminals commercially available as of October 2020 Phoenix Contact Co Ltd CAUTION Do not use the empty terminals NC of the control circuit Doing so may lead to damage of the converter unit and the inverter Wire strip length Cable...

Страница 49: ... terminal with an insulation sleeve compatible with the MTW wire which has a thick wire insulation Applicable for terminals A1 B1 C1 A2 B2 and C2 only Cable gauge mm2 Blade terminal product number Insulation cap product number Crimping tool product number 0 3 to 0 75 BT 0 75 11 VC 0 75 NH 69 3 Insert the wires into a socket When using a single wire or stranded wires without a blade terminal push t...

Страница 50: ... circuits including the 200 V relay sequence circuit For the cables connected to the control circuit terminals connect their shields to the common terminal of the connected control circuit terminal When connecting an external power supply to terminal PC however connect the shield of the power supply cable to the negative side of the external power supply Do not directly earth ground the shield to ...

Страница 51: ...wer supply cable for the control circuit to the upper terminals R1 L11 S1 L21 NOTE When using separate power supplies always remove the jumpers from terminals R1 L11 and S1 L21 The converter unit may be damaged if the jumpers are not removed The voltage should be the same as that of the main control circuit when the control circuit power is supplied from other than the input side of the MC The pow...

Страница 52: ...the converter unit operation is disabled In the initial setting when the main power supply is turned ON during the 24 V external power supply operation a reset is performed in the converter unit then the power supply changes to the main circuit power supply Confirming the 24 V external power supply input During the 24 V external power supply operation the ALARM lamp of the accessory cover blinks W...

Страница 53: ...ower supply Select the power supply and capacity carefully When the wiring length between the external power supply and the converter unit is long the voltage often drops Select the appropriate wiring size and length to keep the voltage in the rated input voltage range In a serial connection of several converter units the current increases when it flows through the converter unit wiring near the p...

Страница 54: ...the RS 485 terminals must be within 5 m To avoid malfunction keep the RS 485 terminal wires away from the control circuit board Name Description RXD1 Converter unit receive RXD1 Converter unit receive RXD2 Converter unit receive for branch RXD2 Converter unit receive for branch TXD1 Converter unit send TXD1 Converter unit send TXD2 Converter unit send for branch TXD2 Converter unit send for branch...

Страница 55: ...urns Install each ferrite core on within 10 cm of the converter unit For branching connect the wires as shown below Master Slave 1 GND Ferrite cores GND TXD1 TXD1 RXD1 RXD1 RXD1 RXD1 RXD2 RXD2 TXD2 TXD2 GND TXD1 TXD1 Master Slave 1 Slave 2 1 GND GND TXD1 TXD1 RXD1 RXD1 RXD2 RXD2 TXD2 TXD2 GND GND TXD1 TXD1 RXD1 RXD1 RXD1 RXD1 RXD2 RXD2 TXD2 TXD2 GND TXD1 TXD1 Ferrite cores Ferrite cores To the tra...

Страница 56: ...following table when fabricating the cable on the user side Keep the total cable length within 20 m Commercially available products as of February 2015 Communication operation Using the PU connector enables communication operation from a personal computer etc When the PU connector is connected with a personal FA or other computer by a communication cable a user program can run to monitor the conve...

Страница 57: ...rs for parallel operation Always set Pr 1001 of the master and reset the converter unit after setting Pr 1001 of the slave and resetting the converter unit If the parameter is set in the reverse order the communication between the master and the slave may not be performed correctly Before the parallel operation set the same values between the master and the slave in Pr 30 Pr 57 Pr 261 and Pr 598 I...

Страница 58: ...rminals and setting Pr 1001 are completed communication between the master slave converter units are started automatically and prepared for the parallel operation When the converter units are ready the Parallel operation ready Y227 signal turns ON For the Y277 signal set 227 positive logic or 327 negative logic in any parameter from Pr 190 to Pr 195 Output terminal function selection to assign the...

Страница 59: ...MEMO 58 ...

Страница 60: ...his chapter explains the precautions for use of this product Always read the instructions before using the equipment 3 1 Electro magnetic interference EMI and leakage currents 60 3 2 Power supply harmonics 66 3 3 Power OFF and magnetic contactor MC 70 3 4 Checklist before starting operation 71 ...

Страница 61: ...e To earth ground leakage currents Take caution as long wiring will increase the leakage current Increasing the motor capacity increases the leakage current Line to line leakage currents Harmonics of leakage currents flowing in static capacitances between the output cables of the inverter or the converter unit may operate the external thermal relay unnecessarily Precautions Use Pr 9 Electronic the...

Страница 62: ...lass Item Breaker designed for harmonic and surge suppression Standard breaker Leakage current Ig1 mA 1 66 5 m 0 11 3 1000 m Leakage current Ign mA 0 without noise filter Leakage current Igi mA 1 without EMC filter For the leakage current of the inverter refer to the following table Leakage current Ig2 mA 1 66 60 m 1 32 3 1000 m Motor leakage current Igm mA 0 36 Total leakage current mA 2 79 6 15 ...

Страница 63: ...e inverter or the converter unit to cause the peripheral devices to malfunction Though the inverter or the converter unit is designed to have high immunity performance it handles low level signals so it requires the following basic techniques Also since the inverter chops outputs at high carrier frequency that could generate electromagnetic noises If these electromagnetic noises cause peripheral d...

Страница 64: ...the power cables magnetic and static induction noises may be propagated to the signal cables to cause malfunction of the devices and the following countermeasures must be taken Install easily affected devices as far away as possible from the inverter or the converter unit Run easily affected signal cables as far away as possible from the I O cables of the inverter or the converter unit Do not run ...

Страница 65: ...100 MHz 100 to 500 MHz 80 150 34 1 TDK 39 1 Product name Lot number 30 1 Cable fixing band mount 13 1 OUTLINE DIMENSION DRAWINGS ZCAT3035 1330 Unit mm Inverter Converter unit Line noise filter Sensor Use 4 core cable for motor power cable and use one cable as earth ground cable Use a twisted pair shielded cable Inverter power supply Do not earth ground shield but connect it to signal common cable ...

Страница 66: ...tched OFF and check that there is no residual voltage using a tester or the like When disconnecting the connector push the fixing tab and pull the connector straight without pulling the cable or forcibly pulling the connector with the tab fixed When installing the connector also engage the fixing tab securely If it is difficult to disconnect the connector use a pair of needle nose pliers etc NOTE ...

Страница 67: ...egrees or less 3 kHz or less High frequency several 10 kHz to 1 GHz order Environment To electric channel power impedance To space distance wiring path Quantitative understanding Theoretical calculation possible Random occurrence quantitative grasping difficult Generated amount Nearly proportional to the load capacity Changes with the current variation ratio Gets larger as switching speed increase...

Страница 68: ... Consumer Guidelines Specific Consumer Guidelines This guideline sets forth the maximum harmonic currents outgoing from a high voltage or especially high voltage receiving consumer who will install add or renew harmonic generating equipment If any of the maximum values is exceeded this guideline requires that consumer to take certain suppression measures Maximum values of outgoing harmonic current...

Страница 69: ...sed DC side 1 4 1 5 7 2 4 1 0 8 0 7 1 6 1 4 P0 Σ Ki Pi kVA Rated capacity Determined by the capacity of the applied motor and found in the table below The rated capacity used here is used to calculate the generated harmonic amount and is different from the power supply capacity required for actual inverter drive Ki Conversion coefficient Refer to page 61 Pi Rated capacity of harmonic generating eq...

Страница 70: ...lses reducing low degree harmonic currents Passive filter AC filter A capacitor and a reactor are used together to reduce impedances at specific frequencies Harmonic currents are expected to be absorbed greatly by using this technique Active filter Active filter This filter detects the current in a circuit generating a harmonic current and generates a harmonic current equivalent to a difference be...

Страница 71: ...wn below always use the start signal ON or OFF of the STF or STR signal to make a start or stop When the power supply is 400 V class install a stepdown transformer Connect the power supply terminals R1 L11 S1 L21 of the control circuit to the input side of the MC to hold an alarm signal when the inverter s protective circuit is activated At this time remove jumpers across terminals R1 L11 and S1 L...

Страница 72: ...urns OFF then confirm that the voltage across the main circuit terminals P and N of the converter unit is low enough using a tester etc The voltage applied to the converter unit I O signal circuits is within the specifications Application of a voltage higher than the permissible voltage to the converter unit I O signal circuits or opposite polarity may damage the I O devices Check the wiring befor...

Страница 73: ...MEMO 72 ...

Страница 74: ...PERATION 73 4 BASIC OPERATION This chapter explains the BASIC OPERATION of this product Always read the instructions before using the equipment 4 1 Operation panel 74 4 2 Monitoring the converter unit status 78 ...

Страница 75: ... STOP RESET key Resets the converter unit when the protective function is activated i Setting dial Changes the parameter settings Press the setting dial to perform the following operations To display a monitored item set in Pr 992 To display a fault history number in the fault history mode j MODE key Switches to different modes Holding this key for 2 seconds locks the operation The key lock is inv...

Страница 76: ...function load factor monitor The last eight fault records can be displayed On the display of the last fault record fault record 1 a decimal point LED is ON When the fault history is empty is displayed Parameter setting mode The present setting displayed Value change Parameter write complete Blink Example Parameter copy Initial value change list Parameter clear All parameter clear Fault history cle...

Страница 77: ...eters such as terminal function selection parameters are not cleared For the details of the uncleared parameters refer to page 170 131 All parameter clear Clears and resets parameter settings to the initial values Terminal function selection parameters are also cleared For the details of the uncleared parameters refer to page 170 131 Fault history clear Deletes the fault history 139 Parameter copy...

Страница 78: ...etting mode Press to choose the parameter setting mode The parameter number read previously appears 3 Selecting the parameter number Turn until Pr 774 appears Press to read the present set value initial value appears 4 Changing the setting value Turn to change the set value to Press to enter the setting and blink alternately Turn to read another parameter Press to show the setting again Press twic...

Страница 79: ...ed in the monitor mode is selectable To set a monitored item as the first monitored item display a monitored item and press for a while NOTE Use Pr 774 Operation panel monitor selection 1 to change the monitored item Refer to page 101 Operation 1 Press to monitor the converter output voltage V appears 2 Press to monitor the input current A appears 3 Press to monitor the electronic thermal relay fu...

Страница 80: ...5 PARAMETER 79 5 PARAMETER This chapter explains the function setting for use of this product Always read the instructions before using the equipment ...

Страница 81: ...999 113 65 H300 Parameter for manufacturer setting Do not set 67 H301 Number of retries at fault occurrence 0 to 10 101 to 110 1 0 97 68 H302 Parameter for manufacturer setting Do not set 69 H303 Retry count display erase 0 1 0 97 75 Reset selection disconnected PU detection reset limit 14 to 17 114 to 117 1 14 88 E100 Reset selection 0 1 0 E101 Disconnected PU detection E107 Reset limit 77 E400 P...

Страница 82: ...999 101 269 E023 Parameter for manufacturer setting Do not set 290 M044 Monitor negative output selection 0 2 4 6 1 0 101 296 E410 Password lock level 0 to 3 5 6 100 to 103 105 106 9999 1 9999 91 297 E411 Password lock unlock 0 to 5 1000 to 9998 9999 1 9999 91 331 N030 Parameter for manufacturer setting Do not set 332 N031 333 N032 N033 334 N034 335 N035 336 N036 337 N037 341 N038 342 N001 Communi...

Страница 83: ...3 889 E421 Free parameter 2 0 to 9999 1 9999 93 891 M023 Cumulative power monitor digit shifted times 0 4 9999 1 9999 101 990 E104 PU buzzer control 0 1 1 1 89 992 M104 Operation panel setting dial push monitor selection 2 8 13 20 25 43 44 55 62 98 1 8 101 997 H103 Fault initiation 0 to 255 9999 1 9999 96 1001 E390 Parallel operation selection 1 2 100 200 300 1 100 56 1006 E020 Clock year 2000 to ...

Страница 84: ...ppear 4 Changing to the group parameter display Turn to change the set value to Parameter display by function group Press to select the parameter setting by function group and blink alternately after the setting is completed Changing example Change the P M101 Pr 774 Operation panel monitor selection 1 Operation 1 Screen at power ON The monitor display appears 2 Parameter setting mode Press to choo...

Страница 85: ...E711 504 Maintenance timer 1 warning output set time 95 E712 686 Maintenance timer 2 95 E713 687 Maintenance timer 2 warning output set time 95 E714 688 Maintenance timer 3 95 E715 689 Maintenance timer 3 warning output set time 95 Pr group Pr Name Refer to page H102 598 Undervoltage level 96 H103 997 Fault initiation 96 H201 872 Input phase loss protection selection 97 H300 65 Parameter for manuf...

Страница 86: ...election 111 A702 57 Restart selection 113 A730 261 Power failure stop selection 114 Pr group Pr Name Refer to page N000 549 Parameter for manufacturer setting Do not set N001 342 Communication EEPROM write selection 117 N002 539 Parameter for manufacturer setting Do not set N020 117 PU communication station number 118 N021 118 PU communication speed 118 N022 119 PU communication data length 118 N...

Страница 87: ... certain period of time Display off mode P E106 Pr 1048 89 To disable the operation panel Operation panel operation selection P E200 Pr 161 90 To set the master slave for the parallel operation Parallel operation selection P E390 Pr 1001 56 To prevent parameter rewriting Parameter write disable selection P E400 Pr 77 90 To restrict parameters with a password Password function P E410 P E411 Pr 296 ...

Страница 88: ...upply to main circuit Refer to page 111 The date set in Pr 1006 to Pr 1008 is also used for the function in the fault history refer to page 139 etc The time can be set The time can only be updated while the converter unit power is ON The real time clock function is enabled using an optional LCD operation panel FR LU08 Pr Name Initial value Setting range Description 1006 E020 Clock year 2000 2000 t...

Страница 89: ...l connector detection function and the reset limit function can be selected Pr Name Initial value Setting range Description 75 Reset selection disconnected PU detection reset limit 14 14 to 17 114 to 117 For the initial setting reset is always enabled PU disconnection is not detected and the reset limit function is disabled E100 Reset selection 0 0 Reset input is always enabled 1 Reset input is en...

Страница 90: ...restart at installation removal of the operation panel power ON OFF of the converter unit or converter reset Display off mode end condition Operation of the operation panel Occurrence of a warning alarm or fault Installation removal of the operation panel power ON OFF of the converter unit or converter reset CAUTION Do not perform a reset while an inverter start signal is being input Doing so will...

Страница 91: ...et at any time Setting through communication is unavailable Disabling parameter write Pr 77 1 Parameter write parameter clear and all parameter clear are disabled Parameter read is enabled The following parameters can be written even if Pr 77 1 Writing parameters Pr 77 2 These parameters can always be written The key operation of the operation panel can be disabled Pr Name Initial value Setting ra...

Страница 92: ...6 9999 When a password is registered parameter reading writing is restricted with the restriction level set in Pr 296 until unlocking NOTE After registering a password the read value of Pr 297 is always one of 0 to 5 appears when a password restricted parameter is read written Even if a password is registered the parameters which the converter unit itself writes such as converter unit parts life a...

Страница 93: ...cannot be performed during the operation For the all parameter clear method refer to the following For the operation panel refer to page 131 for the Mitsubishi inverter protocol of RS 485 communication refer to page 119 Parameter operations during password locking unlocking Correct password will not unlock the restriction NOTE When the password is being locked parameter copy using the operation pa...

Страница 94: ...gree of deterioration of the control circuit capacitor cooling fan and inrush current limit circuit can be diagnosed on the monitor When a part approaches the end of its life an alarm can be output by self diagnosis to prevent a fault Note that the life diagnosis of this function should be used as a guideline only because the life values are theoretical calculations Pr Name Initial value Setting r...

Страница 95: ...ation degree of the control circuit capacitor is displayed in Pr 257 In the operating status the control circuit capacitor life is calculated from the energization time and temperature and is counted down from 100 As soon as the control circuit capacitor life falls below 10 Pr 255 bit 0 is turned ON and also a warning is output to the Y90 signal Life display of the cooling fan If a cooling fan spe...

Страница 96: ...l function selection page 105 The maintenance timer output signal Y95 is output when the converter unit s cumulative energization time reaches the time period set with the parameter MT1 MT2 or MT3 is displayed on the operation panel This can be used as a guideline for the maintenance time of peripheral devices Pr Name Initial value Setting range Description 503 E710 Maintenance timer 1 0 0 1 to 99...

Страница 97: ...fault is not saved in the fault history either Purpose Parameter to set Refer to page To vary the operating level of the undervoltage protective function Undervoltage level P H102 Pr 598 96 To initiate an inverter protective function Fault initiation P H103 Pr 997 96 To disable the I O phase loss protective function Input phase loss protection selection P H201 Pr 872 97 To operate without activati...

Страница 98: ...ter unit When faults occur frequently in the converter unit modify the wiring to enable switchover to the commercial power supply operation using a programmable controller The function is available only when the parameter is set in the master converter unit Settings in the slave does not enable the function When setting Pr 57 set the same setting value in the master and the slave The input phase l...

Страница 99: ...eration ED appears on the operation panel during emergency drive operation The ALM3 signal turns ON when a fault occurs during emergency drive operation FR CC2 P master FR A802 P master FR CC2 P slave FR A802 P slave P N P N MRS X10 RES SD TXD1 TXD2 TXD1 TXD2 RXD1 RXD2 RXD2 RXD1 GND SG RDB RDA IPF RSO FAN SE R L1 S L2 T L3 U V W R1 L11 S1 L21 S1 L21 P N R L1 S L2 T L3 S1 L21 R1 L11 R1 L11 P N U V ...

Страница 100: ...23 setting Description 100 When a critical fault occurs the RDA signal is turned OFF and the RDB signal is turned ON to disable inverter operation 200 Retry operation when a critical fault occurs When a critical fault for which retry is not permitted occurs the RDA signal is turned OFF and the RDB signal is turned ON to disable inverter operation When a critical fault for which retry is not permit...

Страница 101: ...her to output the Fault ALM signal during the retry operation In the initial setting 0 is set the ALM signal is not output during retry ALM3 66 166 Output when a fault occurs during emergency drive operation During emergency drive operation if a fault that does not activate any protective function occurs the signal turns ON for 3 seconds and then turns OFF Input signal status Description Valid OH ...

Страница 102: ...ched to a specified monitor 775 M102 Operation panel monitor selection 2 9999 Input current 776 M103 Operation panel monitor selection 3 9999 Electric thermal relay function load factor 992 M104 Operation panel setting dial push monitor selection 8 Converter output voltage 2 8 13 20 25 43 44 55 62 68 98 Select the monitor to be displayed when the setting dial on the operation panel is pushed 170 M...

Страница 103: ...ion 2 H02 Input current 0 1 A Displays the converter unit input current effective value 8 H08 Converter output voltage 0 1 V Displays the DC bus voltage value 13 H0D Input power 0 1 kW Displays the power at the converter unit input side 20 H14 Cumulative energization time 1 h Displays the cumulative energization time since the converter unit shipment Check how many times the monitor value exceeded...

Страница 104: ...tion panel s setting dial push can be selected with Pr 992 In the initial setting Pr 992 8 the converter output voltage monitor is displayed Operation panel I O terminal monitor Pr 774 to Pr 776 When Pr 774 to Pr 776 55 the I O terminal status can be monitored on the operation panel The LED is ON when the terminal is ON and the LED is OFF when the terminal is OFF The center line of LED is always O...

Страница 105: ...nergization time monitor cannot be cleared NOTE The cumulative energization time does not increase if the power is ON for less than an hour Hiding the decimal places for the monitors Pr 268 The numerical figures after a decimal point displayed on the operation panel may fluctuate during analog input etc The decimal places can be hidden by selecting the decimal digits with Pr 268 NOTE The number of...

Страница 106: ...ectronic thermal O L relay protection E THC is activated when the value reaches 100 106 11 RDA Inverter operation enable NO contact Output when the converter unit operation is ready 107 111 RDB Inverter operation enable NC contact Output when a converter unit fault occurs or the converter is reset inverse to the logic of RDA 17 Y17 Control signal for main circuit power supply MC Output while the s...

Страница 107: ...inal function selection may affect the other functions Set parameters after confirming the function of each terminal 98 198 LF Alarm Output when an alarm fan fault or communication error warning occurs Pr 121 107 125 99 199 ALM Fault Output when the converter unit s protective function is activated to stop the output at fault occurrence The signal output is stopped after a reset 108 206 306 Y206 C...

Страница 108: ...t terminal function selection may affect the other functions Set parameters after confirming the function of each terminal Inverter operation enable signals RDA and RDB and Inverter reset signal RSO The Inverter operation enable RDA signal NO contact turns ON when the converter unit operation is ready and turns OFF when a converter unit fault occurs the Y227 signal is turned OFF refer to page 56 o...

Страница 109: ... assignment using Pr 190 to Pr 195 Output terminal function selection may affect the other functions Set parameters after confirming the function of each terminal Parameters referred to Pr 190 to Pr 195 Output terminal function selection page 105 Pr 290 Monitor negative output selection page 101 The Fault ALM ALM2 signals are output when the converter unit protective function is activated The ALM2...

Страница 110: ...ifferent which may result in an error of wiring or affect other functions Set parameters after confirming the function of each terminal Purpose Parameter to set Refer to page To assign functions to input terminals Input terminal function selection P T700 P T709 P T711 Pr 178 Pr 187 Pr 189 109 To change operation when the OH signal is input OH input selection P T723 Pr 876 110 Use the following par...

Страница 111: ... 187 or Pr 189 Input terminal function selection may affect the other functions Set parameters after confirming the function of each terminal Operation selection for the OH signal Pr 876 The OH signal input status and the Pr 876 setting for the converter operation are as shown below The operation when the external thermal relay input OH signal is input can be changed by the Pr 876 setting Pr Name ...

Страница 112: ...tting range Description 248 A006 Self power management selection 0 0 Self power management function disabled 1 Self power management function enabled main circuit OFF at protective function activation 2 Self power management function enabled main circuit OFF at protective function activation due to a circuit failure or at protective function activation of the slave 30 E300 Reset selection during p...

Страница 113: ...signal turns OFF regardless of the fault contents NOTE Repeated operation of the magnetic contactor due to frequent start and stop or activation of the protective function may shorten the inverter and the converter unit life Changing the terminal assignment using Pr 190 to Pr 195 Output terminal function selection may affect the other functions Set parameters after confirming the function of each ...

Страница 114: ...e activation of the instantaneous power failure protection E IPF or E UVT of the converter unit even when the automatic restart after instantaneous power failure is selected on the inverter side Refer to page 142 for E IPF or E UVT When E IPF or E UVT is activated the Instantaneous power failure undervoltage IPF signal is output The IPF signal is assigned to terminal IPF in the initial status The ...

Страница 115: ...input logic refer to the Instruction Manual of the inverter NOTE When the power failure time deceleration to stop function is selected undervoltage protection E UVT instantaneous power failure protection E IPF and input phase loss protection E ILF are not invalid Changing the terminal assignment using Pr 190 to Pr 195 Output terminal function selection may affect the other functions Set parameters...

Страница 116: ...et or to a telephone connector Doing so may damage the product due to the differences in the electric specifications Purpose Parameter to set Refer to page To start operation via communication Initial setting of operation via communication P N001 Pr 342 117 To operate via communication from PU connector Initial setting of computer link communication PU connector P N020 to P N028 Pr 117 to Pr 124 1...

Страница 117: ...ble PU connector Station 0 Station 0 Computer RS 485 interface terminals Communication cable RJ 45 connector PU connector Converter unit Converter unit Converter unit Operation panel Communication cable RJ 45 connector RJ 45 connector Operation panel connector FR ADP option PU connector Computer Communication cable RJ 45 connector RS 232C connector RS 232C RS 485 converter RS 232C cable Maximum 15...

Страница 118: ...ameter write is performed frequently with the setting unchanged from 0 initial value EEPROM write NOTE Turning OFF the converter unit s power supply clears the modified parameter settings when Pr 342 1 write only to RAM Therefore parameter settings at next power ON will be the ones that are last stored to EEPROM The parameter setting written in RAM cannot be checked on the operation panel The valu...

Страница 119: ...0 equals the communication speed For example if 192 is set the communication speed is 19200 bps N022 PU communication data length 0 0 Data length 8 bits 1 Data length 7 bits N023 PU communication stop bit length 1 0 Stop bit length 1 bit 1 Stop bit length 2 bits 119 PU communication stop bit length data length 1 0 Stop bit length 1 bit Data length 8 bits 1 Stop bit length 2 bits 10 Stop bit length...

Страница 120: ...ceipt of a data error occurrence the converter unit returns reply data c to the computer again The converter unit output is shut off when the number of consecutive data errors exceeds the parameter setting Parameter settings and monitoring are possible by using the Mitsubishi inverter protocol computer link communication via inverter PU connector Item Description Related parameter Communication pr...

Страница 121: ...Whether the CR and LF codes will be present or absent can be selected using Pr 124 CR LF selection Symbol Operation Special monitor write Pr write Converter reset Monitor Pr read a Communication request is sent to the converter unit in accordance with the user program in the computer A1 A A B B b Converter unit data processing time With With Without With With c Reply data from the computer unit Da...

Страница 122: ...e automatically set at the end of a data group on some computers In this case setting must be also made on the converter unit according to the computer Whether the CR and LF codes will be present or absent can be selected using Pr 124 CR LF selection Format Number of characters 1 2 3 4 5 6 7 8 9 B ENQ Converter unit station No Instruction code Sum check Format Number of characters 1 2 3 4 5 6 7 8 ...

Страница 123: ... in the range of 0 to 150 ms in 10 ms increments Example 1 10 ms 2 20 ms When a value other than 9999 is set in Pr 123 PU communication waiting time setting the Pr 123 setting is effective as the delay time Create the communication request data without delay time in the data format The number of characters decreases by 1 Number set in data 10 ms when Pr 123 9999 Pr 123 setting ms when Pr 123 9999 ...

Страница 124: ...Does not accept the received data The converter unit output is not stopped by the fault H8 H9 HA Mode error Parameter write was attempted in other than the computer link operation mode when operation command source is not selected or during converter unit operation Does not accept the received data The fault does not occur HB Instruction code error The specified instruction code does not exist HC ...

Страница 125: ...data transmission time s Refer to the following section Communication speed bps Name Number of bits Item Check time Stop bit length 1 bit 2 bits Various monitored values 12 ms Data length 7 bits 8 bits Parameter read write 30 ms Parity check With 1 bit Parameter clear all clear 5 s Without 0 Reset command No answer In addition to the above 1 start bit is necessary Minimum number of total bits 9 bi...

Страница 126: ...put is shut off When the setting is 9999 communication check signal loss detection is not made When the setting is 0 communication is not possible Setting any value from 0 1 s to 999 8 s will enable signal loss detection To detect signal loss data must be sent from the computer within the communication check time interval for further information on control codes refer to page 122 The converter uni...

Страница 127: ... hDcb DCBlength sizeof DCB Structure size setting hDcb BaudRate 19200 Communication speed 19200 bps hDcb ByteSize 8 Data length 8 bits hDcb Parity 2 Even parity hDcb StopBits 2 Stop bit 2 bits bRet SetCommState hCom hDcb Setting of changed communication information if bRet TRUE Set COM1 port timeout GetCommTimeouts hCom hTim Get current timeout values hTim WriteTotalTimeoutConstant 1000 Write time...

Страница 128: ... conditions Data communication is not started automatically but is made only once when the computer provides a communication request If communication is disabled during operation due to signal cable breakage etc the inverter cannot be stopped When the communication check time interval has elapsed the inverter output will be shut off E PUE The inverter can be coasted to a stop by switching ON the R...

Страница 129: ...e HF3 2 digits A1 C D Fault record Read H74 to H77 H0000 to HFFFF Two latest fault records Refer to page 141 for details on fault record read data 4 digits B E D Converter status monitor extended Read H79 Status of the output signals can be monitored For the details refer to page 130 4 digits B E D Converter status monitor Read H7A 2 digits B E1 D Converter reset Write HFD H9696 Converter unit res...

Страница 130: ...n code HEC HF3 and HFF settings Only H9966 and H55AA all parameter clear are valid during the password lock refer to page 91 4 digits A C D Parameter Read H00 to H63 Refer to the instruction code page 170 and write and or read parameter values as required When setting Pr 100 and later the link parameter extended setting must be set 4 digits B E D Write H80 to HE3 4 digits A C D Link parameter exte...

Страница 131: ...ntaneous power failure undervoltage b6 FAN fan fault signal b7 ABC1 Fault Converter status monitor extended H79 16 bits b0 RDB inverter operation enable signal NC contact b1 Fixed to 0 b2 Fixed to 0 b3 RDA inverter operation enable signal NO contact b4 RSO inverter reset signal b5 IPF instantaneous power failure undervoltage b6 FAN fan fault signal b7 ABC1 Fault b8 to b14 b15 Fault occurrence 0 0 ...

Страница 132: ...ng mode The parameter number read previously appears 3 Selecting the parameter number To perform a parameter clear turn to and to perform all parameter clear turn it to and press initial value appears 4 Parameter clear Turn to change the set value to Press to enter the setting and blink alternately after parameters are cleared Turn to read another parameter Press to show the setting again Press tw...

Страница 133: ...to the operation panel NOTE appears Why Parameter read error Perform the operation from step 3 again Pr CPY setting value Description 0 Initial display 1 RD Copy the source parameters to the operation panel 2 WR The parameters copied to the operation panel can be also copied to the destination converter units 3 VFY Verify parameters in the converter unit and the operation panel Refer to page 134 T...

Страница 134: ...e parameter number read previously appears 3 Selecting the parameter number Turn to parameter copy and press appears 4 Selecting parameter copy Turn to change the set value to then press appears 5 Copying to the converter unit Press to start copying to the converter unit It takes about 60 seconds to copy all the settings During copying blinks 6 Ending copying and blink alternately after copying en...

Страница 135: ...o be verified 3 Screen at power ON The monitor display appears 4 Parameter setting mode Press to choose the parameter setting mode The parameter number read previously appears 5 Selecting the parameter number Turn to parameter copy and press appears 6 Parameter verification Turn to change to the setting value parameter copy verification mode Press Verification of the parameter settings copied to t...

Страница 136: ...s to choose the parameter setting mode The parameter number read previously appears 3 Selecting the parameter number Turn to initial value change list and press appears 4 Checking the initial value change list Turn The parameter numbers that have been changed from their initial value appear in order If is pressed with parameters that have been changed the parameter settings can be changed as they ...

Страница 137: ...MEMO 136 ...

Страница 138: ...ays read the instructions before using the equipment 6 1 Converter unit fault and alarm indications 138 6 2 Reset method for the protective functions 138 6 3 Check and clear of the fault history 139 6 4 Fault history and the list of fault displays 141 6 5 Causes and corrective actions 142 6 6 Check first when you have trouble 150 ...

Страница 139: ... be confirmed before resetting Item Description Fault output signal Opening the magnetic contactor MC provided on the input side of the converter unit at a fault occurrence shuts off the control power to the converter unit therefore the fault output will not be retained Fault or alarm indication When a protective function is activated the operation panel displays a fault indication Operation resta...

Страница 140: ...is installed on the converter unit Fault history mode Monitor mode Parameter setting mode Operation for displaying fault history Eight past faults can be displayed with the setting dial The latest fault is ended by When there is no fault history E0 is displayed Latest fault First fault in past Seventh fault in past Fault history1 Blinking Converter output voltage Blinking Cumulative energization t...

Страница 141: ...ode Press to choose the parameter setting mode The parameter number read previously appears 3 Selecting the parameter number Turn until fault history clear appears Press to read the present set value initial value appears 4 Fault history clear Turn to change the set value to Press to start clear and blink alternately after parameters are cleared Turn to read another parameter Press to show the set...

Страница 142: ...rror 142 to Copy operation error 142 143 Error 143 Operation panel indication Name Refer to page Electronic thermal relay function pre alarm 143 to Maintenance timer 1 to 3 143 Emergency drive in operation 144 Operation panel indication Name Refer to page Fan alarm 145 Operation panel indication Name Data code Refer to page Overvoltage trip 32 H20 145 Converter overload trip electronic thermal rel...

Страница 143: ...arameter write The operation panel and converter unit cannot make normal communication Check point Check the Pr 77 setting Refer to page 90 Check the connection between the operation panel and the converter unit Operation panel indication Er2 Name Parameter write error Description Parameter write was attempted during emergency drive operation Check point Check for any attempt of parameter write du...

Страница 144: ...e at the input side of the converter unit drops When using a separate power source for the control circuit power R1 L11 S1 L21 from the main circuit power R L1 S L2 T L3 this error may appear at turning ON of the main circuit It is not a fault Corrective action Turn OFF the RES signal Check the connection between the operation panel and the converter unit Check the voltage on the input side of the...

Страница 145: ...panel indication ED Name Emergency drive in operation Description Appears during emergency drive operation Check point Emergency drive operation is performed by turning ON the X84 signal Corrective action The display is cleared when the emergency drive operation ends ...

Страница 146: ...ctive action Keep the load stable Check the power supply Operation panel indication E THC Name Converter overload trip electronic thermal relay function Description For the protection of converter unit diode the electronic thermal O L relay is activated in inverse time characteristics against the converter unit input current to shut off the inverter output Check point Check the motor for the use u...

Страница 147: ...e inverter output When undervoltage protection is activated the IPF signal is output Refer to page 113 Check point Check if a high capacity motor is driven Corrective action Check the power supply system equipment such as the power supply If the problem still persists after taking the above measure contact your sales representative Operation panel indication E ILF Name Input phase loss Description...

Страница 148: ...tput is shut off if communication errors occur consecutively for the permissible number of retries or more during the RS 485 communication from the PU connector with Pr 121 Number of PU communication retries 9999 The inverter output is shut off if communication is broken for the period of time set in Pr 122 PU communication check time interval during the RS 485 communication from the PU connector ...

Страница 149: ...h insufficient voltage is supplied to the 24 V input circuit for a long time the internal circuit may heats up Input power at correct voltage although it will not damage the converter unit Operation panel indication E IOH Name Inrush current limit circuit fault Description The inverter output is shut off when the resistor of the inrush current limit circuit is overheated The inrush current limit c...

Страница 150: ...mprove after taking the above measure contact your sales representative Operation panel indication EV Name 24 V external power supply operation Description Blinks when the main circuit power supply is off and the 24 V external power supply is being input Check point Power is supplied from a 24 V external power supply Corrective action Turning ON the power supply main circuit of the converter unit ...

Страница 151: ... a magnetic contactor MC Check for the decreased input voltage input phase loss and wiring If only the control power is ON when using a separate power source for the control circuit turn ON the main circuit power 50 Checkpoints Cause Countermeasure Refer to page Main circuit Control Circuit Wiring or installation is improper Check for the wiring and the installation Power lamp is lit when power is...

Страница 152: ...efer to the Instruction Manual Detailed of the inverter Checkpoints Cause Countermeasure Refer to page Parameter setting Parameter is disabled by the Pr 77 Parameter write selection setting Check the Pr 77 setting 90 Key lock mode is enabled by the Pr 161 Key lock operation selection setting Check the Pr 161 setting 90 Checkpoints Cause Countermeasure Refer to page Main circuit Wiring or installat...

Страница 153: ...MEMO 152 ...

Страница 154: ...S FOR MAINTENANCE AND INSPECTION This chapter explains the PRECAUTIONS FOR MAINTENANCE AND INSPECTION for this product Always read the instructions before using the equipment 7 1 Inspection item 154 7 2 Measurement of main circuit voltages currents and powers 161 ...

Страница 155: ...nals P and N of the converter unit is not more than 30 VDC using a tester etc 7 1 Inspection item 7 1 1 Daily inspection Basically check for the following faults during operation Motor operation fault Improper installation environment Cooling system fault Abnormal vibration abnormal noise Abnormal overheat discoloration 7 1 2 Periodic inspection Check the areas inaccessible during operation and re...

Страница 156: ...cturer Terminal block Check for a damage Stop the equipment and contact the manufacturer Smoothing aluminum electrolytic capacitor 1 Check for liquid leakage Contact the manufacturer 2 Check for safety valve projection and bulge Contact the manufacturer 3 Visual check and judge by the life check of the main circuit capacitor Refer to page 158 Relay contactor Check that the operation is normal and ...

Страница 157: ...llation environment Consult us for periodic inspection NOTE Continuous use of a leaked deformed or degraded smoothing aluminum electrolytic capacitor as shown in the table above may lead to a burst breakage or fire Replace such capacitor without delay Display Indication 1 Check that display is normal Contact the manufacturer 2 Check for stain Clean Meter Check that reading is normal Stop the equip...

Страница 158: ...same although these values are not constant depending on the module type and tester type the modules are without fault Semiconductor device numbers and terminals to be checked Assumes the use of an analog meter 7 1 5 Cleaning Always run the converter unit in a clean status When cleaning the converter unit gently wipe dirty areas with a soft cloth immersed in neutral detergent or ethanol NOTE Do no...

Страница 159: ...verter unit parts life display The converter unit diagnoses the control circuit capacitor cooling fan and inrush current limit circuit by itself and estimates their lives The self diagnostic warning is output when the life span of each part is near its end It gives an indication of replacement time The life warning output can be used as a guideline for life judgment NOTE Refer to page 93 to perfor...

Страница 160: ...e number of cooling fans differs according to the converter unit capacity Reinstallation 1 After confirming the orientation of the fan reinstall the fan so that the AIR FLOW faces up 2 For reconnection of the fan refer to the above figure The tightening torque of the fan fixing screws is 0 73 N m NOTE Installing the fan in the opposite direction of air flow can cause the converter unit life to be ...

Страница 161: ...e To prevent faults from occurring relays must be replaced when they have reached the maximum number of switching operations switching life The control terminal block must be replaced in case of failure of the relay connected to the relay output terminals A1 B1 and C1 After installing a new control terminal block set up the control logic for input signals with the jumper connector control logic se...

Страница 162: ...er supply voltage V1 Across R L1 and S L2 S L2 and T L3 T L3 and R L1 Digital power meter designed for inverter Commercial power supply Within permissible AC voltage fluctuation Refer to page 166 Power supply side current I1 R L1 S L2 T L3 line current Power supply side power P1 R L1 S L2 T L3 and Across R L1 and S L2 S L2 and T L3 T L3 and R L1 P1 W11 W12 W13 3 wattmeter method Power supply side ...

Страница 163: ...e output frequency varies Hence it is recommended to monitor values on the operation panel 7 2 4 Example of measuring converter unit input power factor Calculate using effective power and apparent power A power factor meter cannot indicate an exact value 7 2 5 Measurement of converter output voltage across terminals P and N The output voltage of the converter is output across terminals P and N and...

Страница 164: ... circuit Use a 500 VDC megger NOTE Before performing the insulation resistance test on the external circuit disconnect the cables from all terminals of the converter unit so that the test voltage is not applied to the converter unit For the continuity test of the control circuit use a tester high resistance range and do not use the megger or buzzer 7 2 7 Withstand voltage test Do not conduct a wit...

Страница 165: ...MEMO 164 ...

Страница 166: ... SPECIFICATIONS This chapter explains the SPECIFICATIONS of this product Always read the instructions before using the equipment 8 1 Converter unit rating 166 8 2 Common specifications 166 8 3 Outline dimension drawings 167 ...

Страница 167: ...t for control circuit Output signal Open collector output five terminals Relay output one terminal Inverter operation enable positive logic negative logic Instantaneous power failure undervoltage Inverter reset Fan fault output Fault The output signal can be changed using Pr 190 to Pr 195 Output terminal function selection Operation panel Operating status Converter output voltage Input current Ele...

Страница 168: ...ine dimension drawings 8 3 1 Converter unit outline dimension drawings Do not remove the cover on the side of the converter unit FR CC2 H400K H450K H500K H560K P Unit mm 3 12 hole 8 25 185 185 23 12 100 200 600 440 4 5 4 5 200 100 15 1550 17 17 1546 15 1580 ...

Страница 169: ...MEMO 168 ...

Страница 170: ...ix 2 Instructions for compliance with the EU Directives 172 Appendix 3 Instructions for UL and cUL 176 Appendix 4 Instructions for EAC 178 Appendix 5 Restricted Use of Hazardous Substances in Electronic and Electrical Products 179 Appendix 6 Referenced Standard Requirement of Chinese standardized law 179 Appendix 7 Compliance with the UK certification scheme 180 ...

Страница 171: ...187 OH terminal function selection 1B 9B 2 189 RES terminal function selection 1D 9D 2 190 RDB terminal function selection 1E 9E 2 191 RDA terminal function selection 1F 9F 2 192 IPF terminal function selection 20 A0 2 193 RSO terminal function selection 21 A1 2 194 FAN terminal function selection 22 A2 2 195 ABC1 terminal function selection 23 A3 2 248 Self power management selection 38 B8 2 255 ...

Страница 172: ...1 58 D8 8 889 Free parameter 2 59 D9 8 891 Cumulative power monitor digit shifted times 5B DB 8 990 PU buzzer control 5A DA 9 992 Operation panel setting dial push monitor selection 5C DC 9 997 Fault initiation 61 E1 9 1001 Parallel operation selection 01 81 A 1006 Clock year 06 86 A 1007 Clock month day 07 87 A 1008 Clock hour minute 08 88 A 1048 Display off waiting time 30 B0 A Pr Name Instructi...

Страница 173: ...C Directive and affix the CE marking on the converter unit EMC Directive 2014 30 EU Standard s EN61800 3 2004 A1 2012 Second environment PDS Category C3 Please ensure you chose the right converter unit for the intended environment Ensure the converter unit is suitable for the environment in which it is to be used when using it in residential areas The installer shall provide a guide for installati...

Страница 174: ... using a residual current device RDC or residual current monitor RDM connect a type B RCD or RCM to the power supply side Use the converter unit under the conditions of overvoltage category II usable regardless of the earth ground condition of the power supply overvoltage category III usable with the earth neutral system power supply 400 V class only and pollution degree 2 or lower specified in IE...

Страница 175: ...rms Symmetrical Amperes 500 V Maximum EU RoHS Directive We have declared that our converter units are compliant to the EU RoHS Directive 2011 65 EU and affix the CE marking on the converter units FR CC2 P H400K H450K H500K H560K Rated fuse voltage V 500 V or more Fuse maximum allowable rating A 1350 1500 1800 1800 Converter model Fuse type Model Manufacturer Rating FR CC2 H400K P UL Recognized Hig...

Страница 176: ...voltage multiplied by The power supply capacity is the value when at the rated output current It varies by the impedance at the power supply side including those of the input reactor and cables The permissible voltage imbalance ratio is 3 or less Imbalance ratio highest voltage between lines average voltage between three lines average voltage between three lines 100 Model FR CC2 H P 400K 450K 500K...

Страница 177: ...e United States Class T Class J Class CC or Class L fuse must be provided in accordance with the National Electrical Code and any applicable local codes For installation in Canada Class T Class J Class CC or Class L fuse must be provided in accordance with the Canadian Electrical Code and any applicable local codes Wiring to the power supply and the motor Refer to the National Electrical Code Arti...

Страница 178: ...voltage multiplied by The power supply capacity is the value when at the rated output current It varies by the impedance at the power supply side including those of the input reactor and cables The permissible voltage imbalance ratio is 3 or less Imbalance ratio highest voltage between lines average voltage between three lines average voltage between three lines 100 Model FR CC2 H P 400K 450K 500K...

Страница 179: ...al Regulations CU TR and the EAC marking must be affixed to the products For information on the country of origin manufacture year and month and authorized sales representative importer in the CU area of this product refer to the following Country of origin indication Check the rating plate of the product Refer to page 8 Example MADE IN JAPAN Manufactured year and month Check the SERIAL number ind...

Страница 180: ...China 电器电子产品有害物质限制使用标识要求 本产品中所含有的有害物质的名称 含量 含有部件如下表所示 产品中所含有害物质的名称及含量 上表依据 SJ T11364 的规定编制 表示该有害物质在该部件所有均质材料中的含量均在 GB T26572 规定的限量要求以下 表示该有害物质在该部件的至少一种均质材料中的含量超出 GB T26572 规定的限量要求 即使表中记载为 根据产品型号 也可能会有有害物质的含量为限制值以下的情况 根据产品型号 一部分部件可能不包含在产品中 Appendix 6 Referenced Standard Requirement of Chinese standardized law This Product is designed and manufactured accordance with following Chinese standards 环境保护...

Страница 181: ...n England Wales and Scotland from January 1 2021 after the departure of the UK from the EU on January 31 2020 We declare that this product conforms with the related technical requirements under UK legislation and affix the UKCA UK Conformity Assessed marking on the product Approval conditions are the same as those for the EU Directives Refer to page 172 ...

Страница 182: ...e cause with a scientific technology that was not available at the time of the shipment of the Product from our company any other failures which we are not responsible for or which you acknowledge we are not responsible for 2 Term of warranty after the stop of production 1 We may accept the repair at charge for another seven 7 years after the production of the product is discontinued The announcem...

Страница 183: ...number Revision Nov 2016 IB NA 0600657ENG A First edition Jan 2022 IB NA 0600657ENG B Added Emergency drive Pr 67 Number of retries at fault occurrence Pr 514 Emergency drive dedicated retry waiting time Pr 515 Emergency drive dedicated retry count Pr 523 Emergency drive selection IB NA 0600657ENG B ...

Страница 184: ...IB NA 0600657ENG B 2201 MEE Printed in Japan Specifications subject to change without notice HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Отзывы: