Terminal connection diagrams
27
2
2.4
Terminal connection diagrams
When the sink logic is selected
When using separate power supply for the control circuit, remove the jumpers from R1/L11 and S1/L21.
The function of these terminals can be changed with the input terminal assignment
(Pr.178, Pr.187, Pr.189)
.
The function of these terminals can be changed with the output terminal assignment
(Pr.195)
.
The function of these terminals can be changed with the output terminal assignment
(Pr.190 to Pr.194).
The connector is for manufacturer setting. Do not use.
Plug-in options cannot be used.
For manufacturer setting. Do not use.
To use the RDA signal of the converter unit, select the NC contact input specification for the input logic of MRS signal or X10 signal of the
inverter.
To use the RDB signal of the converter unit, select the NO contact input specification for the input logic of MRS signal or X10 signal of the
inverter. (For changing the input logic, refer to the Instruction Manual of the inverter.)
NOTE
• To prevent a malfunction due to noise, keep the signal cables 10 cm or more away from the power cables. Also, separate the
main circuit cables at the input side from the main circuit cables at the output side.
• After wiring, wire offcuts must not be left in the inverter or the converter unit.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter and the converter unit clean.
When drilling mounting holes in an enclosure etc., take caution not to allow chips and other foreign matter to enter the
inverter or the converter unit.
Three-phase
AC power
supply
MCCB
Jumper
R/L1
S/L2
T/L3
R1/L11
S1/L21
PC
24VDC power supply
(Common for external power supply transistor)
Reset
External thermal relay input
Contact input
Inverter operation enable
(NO contact)
Inverter operation enable
(NC contact)
Inverter reset
Instantaneous
power failure
Cooling fan fault
Open collector output common
Sink/source common
Control input signals
(No voltage input allowed)
∗
2
Relay output
(Fault output)
C1
B1
A1
Earth
(Ground)
Open collector output
∗
4
Contact input common
Main circuit terminal
Control circuit terminal
MC
Main circuit
Relay output
∗
3
TXD+
Terminating
resistor
TXD-
RXD+
RXD-
GND
(SG)
GND
RS-485 terminals
PU
connector
SINK
SOURCE
Connector for manufacturer setting
RES
OH
RDI
SD
RDA
RDB
RSO
MRS
(X10)
IPF
FAN
SE
VCC
5V (Permissible load
current 100mA)
Sink logic
Inverter
∗
1
Connector 1
N/-
P/+
Control circuit
DC reactor
+24
24V external power
supply input
Common terminal
SD
RES
SD
EMC filter
ON/OFF
connecter
ON
OFF
∗
6
USB
mini B
connector
∗
5
N/-
P/+
88R
88S
∗
7
Data reception
Data transmission
∗
8
ON
OFF
24V
Inrush current
limit circuit