(M) Monitor display and monitor output signal
103
5
GROUP
M
The total input power value of the master and slave converter units is displayed.
The total cumulative power value of the master and slave converter units is displayed.
While the input current of the converter unit for 12-phase rectification is monitored, a total amount of input current in the star-delta connections is
shown as an effective value of input current. (It is not an effective value of input current in each star/delta connection.)
Monitor display for operation panel (Pr.774 to Pr.776)
• The monitor displayed at power ON is the first monitor (the converter output voltage monitor in the initial setting). Display
the monitor that will be the first monitor, and continue pressing
for 1 s. (To return to the converter output voltage
monitor, display the converter output voltage monitor and press
for 1 s.)
•
Pr.774
sets the first monitor,
Pr.775
sets the second monitor, and
Pr.776
sets the third monitor to be displayed.
NOTE
• The converter unit set in slave 1 (
Pr.1001 Parallel operation selection
= "1") / slave 2 (
Pr.1001
="2") displays SLV.1 (parallel
operation slave 1) / SLV.2 (parallel operation slave 2) on the first monitor screen regardless of the
Pr.774
setting. (Refer to
.)
Operation panel setting dial push monitor selection (Pr.992)
• The monitored item to be displayed at the operation panel's setting dial push can be selected with
Pr.992
. In the initial
setting (
Pr.992
= "8"), the converter output voltage monitor is displayed.
Operation panel I/O terminal monitor (Pr.774 to Pr.776)
• When
Pr.774 to Pr.776
= "55", the I/O terminal status can be monitored on the operation panel.
• The LED is ON when the terminal is ON, and the LED is OFF when the terminal is OFF. The center line of LED is always
ON.
• On the I/O terminal monitor (
Pr.774 to Pr.776
= "55"), the upper LEDs denote the input terminal state, and the lower LEDs
denote the output terminal state.
Cumulative power monitor and clear (Pr.170, Pr.891)
• On the cumulative power monitor (
Pr.774 to Pr.776
= "25"), the input power monitor value is added up and updated in 100
ms increments. (The values are saved in EEPROM every hour.)
• Display increments and display ranges of the operation panel and communication (RS-485 communication) are as
indicated below.
Pr.774 to Pr.776 setting
Monitor description
55
Displays the I/O terminal ON/OFF state of the converter unit.
Communication
Range
Unit
Range
Unit
Pr.170 = 10
Pr.170 = 9999
0 to 999.99 kWh
0.01 kWh
0 to 9999 kWh
0 to 65535 kWh
(initial value)
1 kWh
1000.0 to 9999.9 kWh
0.1 kWh
10000 to 99999 kWh
1 kWh
Input current monitor
Electronic thermal relay
function load factor monitor
Converter output
voltage monitor
• Power-on monitor (first monitor)
• Second monitor
• Third monitor
• Fault monitor
With fault
Center line is always ON
Input terminal
- Display example -
When signals OH, ABC1
and RDB are ON
Output terminal
OH
RDB
ABC1
RSO
RDA
IPF
FAN
RDI
RES