3. PRECAUTIONS FOR USE OF THE CONVERTER UNIT
3.1 Electro-magnetic interference (EMI) and leakage currents
3
PRECAUTIONS FOR USE OF THE CONVERTER
UNIT
This chapter explains the precautions for use of this product.
Always read the instructions before use.
3.1
Electro-magnetic interference (EMI) and leakage
currents
3.1.1
Leakage currents and countermeasures
Capacitances exist between the I/O cables or other cables of the inverter or the converter unit and earth, and in the motor,
through which a leakage current flows. Since its value depends on the static capacitances, carrier frequency, etc., low acoustic
noise operation at the increased carrier frequency of the inverter will increase the leakage current. Therefore, take the following
countermeasures. Select the earth leakage current breaker according to its rated sensitivity current, independently of the
carrier frequency setting.
To-earth (ground) leakage currents
Leakage currents may flow not only into the inverter's own line or the converter unit's own line but also into the other lines
through the earthing (grounding) cable, etc. These leakage currents may operate earth leakage circuit breakers and earth
leakage relays unnecessarily.
Countermeasures
• If the carrier frequency setting is high, decrease the
Pr.72 PWM frequency selection
setting.
Note that motor noise increases. Selecting
Pr.240 Soft-PWM operation selection
makes the sound inoffensive.
• By using earth leakage circuit breakers designed for harmonic and surge suppression in the inverter's own line, converter
unit's own line and other line, operation can be performed with the carrier frequency kept high (with low noise).
To-earth (ground) leakage currents
• Take caution as long wiring will increase the leakage current. Decreasing the carrier frequency of the inverter reduces the
leakage current.
• High motor capacity will increase the leakage current.
Line-to-line leakage currents
Harmonics of leakage currents flowing in static capacitances between the output cables of the inverter or the converter unit
may operate the external thermal relay unnecessarily.
Countermeasures
• Use
Pr.9 Electronic thermal O/L relay
.
• If the carrier frequency setting is high, decrease the
Pr.72 PWM frequency selection
setting.
Note that motor noise increases. Selecting
Pr.240 Soft-PWM operation selection
makes the sound inoffensive.
To ensure that the motor is protected against line-to-line leakage currents, it is recommended to use a temperature sensor
to directly detect motor temperature.
Power
supply
Thermal relay
Line-to-line static
capacitances
MCCB
MC
Line-to-line leakage currents path
Motor
M
Inverter
Converter
unit
Содержание FR-CC2-N Series
Страница 61: ...60 3 PRECAUTIONS FOR USE OF THE CONVERTER UNIT 3 4 Checklist before starting operation MEMO ...
Страница 137: ...136 5 PARAMETERS 5 10 Checking parameters changed from their initial values initial value change list MEMO ...
Страница 153: ...152 6 PROTECTIVE FUNCTIONS 6 6 Check first when you have a trouble MEMO ...
Страница 165: ...164 7 PRECAUTIONS FOR MAINTENANCE AND INSPECTION 7 2 Measurement of main circuit voltages currents and powers MEMO ...
Страница 171: ...170 8 SPECIFICATIONS 8 3 Outline dimension drawings MEMO ...