17
3
3.2 Wiring
Use the network connection cable which supports 12.0 Mbps communication.
(1) Strip off the sheath of the PROFIBUS communication dedicated cable and wind wires and shield
cables to use.
Strip off the sheath for the below length. If the length of the sheath peeled is too long, a short circuit
may occur with neighboring wires. If the length is too short, wires might come off.
Wire the stripped cable after twisting it to prevent it from becoming loose. In addition, do not solder it.
Use a ferrule terminal as necessary.
When using the ferrule terminal, use care so that the twisted wires do not come out.
NOTE
• Ferrule terminal commercially available (as of February 2012. The product may be changed without notice.)
Cable stripping length
Terminal
screw size
Wire size (mm
2
)
Ferrule terminal model
Manufacturer
Crimping tool
name
with insulation sleeve
without insulation sleeve
M2
0.3 to 0.5
Al 0,5-6WH
A 0,5-6
Phoenix Contact
Co.,Ltd.
CRIMPFOX 6
5 mm
Crumpled tip
Wires are not inserted
into the sleeve
Unstranded
wires
Damaged
Wire
Wire
Sleeve
Sleeve
0 to 0.5 mm
0 to 0.5 mm
Содержание FR-A8NP