26
4.4.3
Setting output signals
Set the output signals to be monitored. Set
Pr.306
to output the same signal from terminals AM0 and AM1, and
Pr.306
and
Pr.310
to output different signals. The AM0 terminal can be used for negative output (from -10 VDC to +10 VDC). The settings
of
Pr.306 and Pr.310
are the same as those of
Pr.54 FM/CA terminal function selection
and
Pr.158 AM terminal function
selection
. For the details of
Pr.54 and Pr.158
, refer to the Instruction Manual (Detailed) of the inverter.
4.4.4
Analog meter voltage negative output selection (Pr.1019)
The output from the terminal AM0 (analog voltage output) can be displayed with minus signs on the monitor. For the monitored
items that can have minus signs, refer to the description of
Pr.54 FM/CA terminal function selection
and
Pr.158 AM terminal
function selection
in the Instruction Manual (Detailed) of the inverter.
NOTE
• When terminal AM0 (analog voltage output) is “output with a minus sign”, the output will be within the -10V DC to +10V
DC range.
Connect the meter with which output level is matched.
• Parameter unit (FR-PU07) displays only positive values.
• When the remote output 1 to 4 is set to the terminal AM0 (
Pr.306
= "87 to 90"), regardless of the
Pr.1019
setting,
minus outputs can be made.
Pr.1019 setting
Minus sign output from terminal AM0
0 (initial value)
Output without minus sign (positive values only)
1
Output with minus sign.