3.4 Parameter setting
Setting output signals
Use
Pr.320 to Pr.322
to assign signals to the terminals ABC (1 to 3). The settings of
Pr.320 to Pr.322
are the same as those of
Pr.190 to Pr.196 (output terminal function selection)
. For the details of
Pr.190 to Pr.196
, refer to the Instruction Manual
(Detailed) of the inverter.
NOTE
• All the outputs are shut off when the protective functions (E.1 to E.3) are activated.
• Negative logic cannot be set.
Adjusting the output terminal response level (Pr.418)
• The response level of the output terminals can be delayed in a range of 5 to 50 ms. (Operation example for the RUN signal.)
NOTE
• The response level is not adjusted while
Pr.418
= "9999".
• When
Pr.157 OL signal output timer
is set for the Overload warning (OL) signal output, the OL signal is output when
the set time of (
Pr.157
+
Pr.418
) elapses.
Time
RUN
Pr.418
= 9999
ON
OFF
RUN
Pr.418
≠ 9999
ON
OFF
Pr.418
Pr.418
Output frequency