Inverter fault and indications
92
4.1
Inverter fault and indications
• When a fault occurs in the inverter, a protective function is automatically activated to shut off the inverter output and show
an indication on the operation panel of the inverter.
• When any fault occurs, take an appropriate corrective action, then reset the inverter, and resume the operation. Restarting
the operation without a reset may break or damage the inverter.
• When a protective function is activated, note the following points.
• Inverter fault or alarm indications are categorized as below.
NOTE
• For the details of fault displays and other malfunctions, refer to the FR-A800 Instruction Manual (Detailed).
• The past eight faults can be displayed on the operation panel. (Fault history) (For operation, refer to
4.2
Reset method for the protective functions
Reset the inverter by performing any of the following operations. Note that the accumulated heat value of the electronic
thermal relay function and the number of retries are cleared (erased) by resetting the inverter.
The inverter recovers about 1 s after the reset is released.
NOTE
• OFF status of the start signal must be confirmed before resetting the inverter fault. Resetting an inverter fault with the start
signal ON restarts the motor suddenly.
Item
Description
Fault output signal
Opening the magnetic contactor (MC) provided on the input side of the inverter at a fault occurrence
shuts off the control power to the inverter, therefore, the fault output will not be retained.
Fault or alarm indication
When a protective function is activated, the operation panel displays a fault indication.
Operation restart method
While a protective function is activated, the inverter output is kept shutoff. Reset the inverter to restart
the operation.
Displayed item
Description
Error message
A message regarding an operational fault and setting fault by the operation panel (FR-DU08) and
parameter unit (FR-PU07) is displayed. The inverter does not trip.
Warning
The inverter does not trip even when a warning is displayed. However, failure to take appropriate
measures will lead to a fault.
Alarm
The inverter does not trip. The Alarm (LF) signal can also be output with a parameter setting.
Fault
A protective function is activated to trip the inverter and output the Fault (ALM) signal.
• On the operation panel, press
to reset the inverter.
(This may only be performed when a fault occurs.)
• Switch power OFF once, then switch it ON again.
• Turn ON the Inverter reset (RES) signal for 0.1 s or more. (If the
RES signal is kept ON, "Err" appears (blinks) to indicate that the
inverter is in a reset status.)
ON
OFF
SD
Inverter
RES
Содержание FR-A842-07700