Peripheral devices
14
2.1
Peripheral devices
2.1.1
Inverter and peripheral devices
NOTE
• To prevent an electric shock, always earth (ground) the motor, the inverter, and the converter unit.
• Do not install a power factor correction capacitor or surge suppressor or capacitor type filter on the inverter's output side. Doing
so will cause the inverter to trip or the capacitor and surge suppressor to be damaged. If any of the above devices is connected,
immediately remove it. When installing a molded case circuit breaker on the output side of the inverter, contact the manufacturer
of the molded case circuit breaker.
• Electromagnetic wave interference
The input/output (main circuit) of the inverter or the converter unit includes high frequency components, which may interfere
with the communication devices (such as AM radios) used near the inverter or the converter unit. In this case, activating the
EMC filter of the converter unit may minimize interference. (Refer to
.)
• For details of options and peripheral devices, refer to the respective Instruction Manual.
Earth
(Ground)
R/L1 S/L2 T/L3
N/-
N/-
P/+
P/+
N/-
P/+
P/+
P/+
PR
PR
: Install these options as required.
U V W
(d) Moulded case
circuit breaker
(MCCB) or earth
leakage current
breaker (ELB),
fuse
(l) Noise filter
(g) Noise filter
(h) High power factor converter
(FR-HC2)
(j) Resistor unit
(MT-BR5)
(i) Brake unit
(FR-BU2)
(e) Magnetic
contactor
(MC)
(a) Inverter
(FR-A802)
(b) Converter unit
(FR-CC2)
(c) Three-phase AC power supply
(k) USB connector
Personal computer
(FR Configurator 2)
USB
USB host
(A connector)
USB device
(Mini B connector)
Communication
status indicator
(LED)(USB host)
Earth
(Ground)
(m) Induction
motor
(f) AC reactor
(FR-HAL)
Earth
(Ground)