Causes and corrective actions
Protective functions
6 - 36
Operation panel
indication
E.IAH
FR-LU-08
Abnormal Intnl Temp
Name
Abnormal internal temperature (IP55 compatible models only)
Description
The inverter trips when the inverter internal temperature reaches the specified value or higher.
Check point
앫
Check for too high surrounding air temperature.
앫
Check if the internal air circulation fan or the cooling fan stops due to a fault.
Corrective action
앫
Install an inverter suitable for the installation environment. (Refer to the Instruction Manual
(Hardware) of the FR-A806.)
앫
Replace the internal air circulation fan or the cooling fan.
Operation panel
indication
E.LCI
FR-LU-08
4 mA input fault
Name
4 mA input fault
Description
The inverter trips when the analog input current is 2 mA or less for the time set in Pr. 778 "4 mA
input check filter". This function is available when Pr. 573 "4 mA input check selection" = "2 or 3".
(Refer to page 5-416.) This function is not available in the initial status.
Check point
앫
Check for a break in the wiring for the analog current input.
앫
Check that the Pr. 778 setting is not too short.
Corrective action
앫
Check the wiring for the analog current input.
앫
Set the Pr. 778 setting larger.
Operation panel
indication
E.PCH
FR-LU-08
Pre-charge fault
Name
Pre-charge fault
Description
앫
The inverter trips when the pre-charge time exceeds Pr. 764 "Pre-charge time limit".
앫
The inverter trips when the measured value exceeds Pr. 763 "Pre-charge upper detection
level" during pre-charging.
앫
This function is available when Pr. 764 and Pr. 763 are set. This protective function is not
available in the initial status.
Check point
앫
Check that the Pr. 764 setting is not too short.
앫
Check that the Pr. 763 setting is not too small.
앫
Check that the Pr. 127 "PID control automatic switchover frequency" setting is not too low.
앫
Check for a break in the connection to the pump.
Corrective action
앫
Set the Pr. 764 setting longer.
앫
Set the Pr. 763 setting larger.
앫
Set the Pr. 127 setting higher.
앫
Check the connection to the pump.
Operation panel
indication
E.PID
FR-LU-08
PID signal fault
Name
PID signal fault
Description
The inverter trips if the measured value exceeds the PID upper limit or PID lower limit parameter
setting, or the absolute deviation value exceeds the PID deviation parameter setting during PID
control.
Set this function in Pr. 131 "PID upper limit", Pr. 132 "PID lower limit", Pr. 553 "PID deviation limit",
and Pr. 554 "PID signal operation selection". (Refer to page 5-543.) This protective function is not
available in the initial status.
Check point
앫
Check the meter for a failure or break.
앫
Check that the parameter settings are correct.
Corrective action
앫
Check that the meter has no failure or break.
앫
Set the parameters correctly.
Содержание FR-A820-00046 (0.4K)
Страница 2: ......
Страница 4: ......
Страница 144: ...System configuration for Ethernet communication FR A800 E Installation and wiring 2 114 ...
Страница 202: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 1090: ...Check first when you have a trouble Protective functions 6 50 ...
Страница 1110: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 1188: ...EC Declarations of Conformity Appendix A 48 A 7 EC Declarations of Conformity A 7 1 FR A820 FR A840 FR A842 series ...
Страница 1189: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Страница 1190: ...EC Declarations of Conformity Appendix A 50 ...
Страница 1191: ...Appendix EC Declarations of Conformity FR A800 A 51 ...
Страница 1192: ...EC Declarations of Conformity Appendix A 52 ...
Страница 1193: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Страница 1194: ...EC Declarations of Conformity Appendix A 54 ...
Страница 1195: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Страница 1196: ...EC Declarations of Conformity Appendix A 56 ...
Страница 1197: ...Appendix EC Declarations of Conformity FR A800 A 57 ...
Страница 1198: ...EC Declarations of Conformity Appendix A 58 ...
Страница 1199: ...Appendix EC Declarations of Conformity FR A800 A 59 ...
Страница 1200: ...EC Declarations of Conformity Appendix A 60 ...
Страница 1201: ...Appendix EC Declarations of Conformity FR A800 A 61 ...
Страница 1202: ...EC Declarations of Conformity Appendix A 62 ...
Страница 1203: ...Appendix EC Declarations of Conformity FR A800 A 63 ...
Страница 1204: ...EC Declarations of Conformity Appendix A 64 ...
Страница 1205: ...Appendix EC Declarations of Conformity FR A800 A 65 ...
Страница 1206: ...EC Declarations of Conformity Appendix A 66 ...
Страница 1207: ...Appendix EC Declarations of Conformity FR A800 A 67 ...
Страница 1208: ...EC Declarations of Conformity Appendix A 68 ...
Страница 1209: ...Appendix EC Declarations of Conformity FR A800 A 69 ...
Страница 1210: ...EC Declarations of Conformity Appendix A 70 ...
Страница 1211: ...Appendix EC Declarations of Conformity FR A800 A 71 ...
Страница 1212: ...EC Declarations of Conformity Appendix A 72 A 7 2 FR A846 series ...
Страница 1213: ...Appendix EC Declarations of Conformity FR A800 A 73 ...
Страница 1214: ...EC Declarations of Conformity Appendix A 74 ...
Страница 1215: ...Appendix EC Declarations of Conformity FR A800 A 75 ...
Страница 1216: ...EC Declarations of Conformity Appendix A 76 A 7 3 Frequency inverters with option unit FR A8NP ...
Страница 1217: ......