Parameters
(G) Control parameters
FR-A800
5 - 667
Braking operation selection at the time of Real sensorless vector control (Pr. 850 = "0, 1")
The braking operation at the time of the Real sensorless vector control can be selected between the
DC injection brake (initial value) or the Zero speed control.
By setting Pr. 850 "Brake operation selection" = "1", zero speed control will be performed under the
frequency set in Pr. 10 "DC injection brake operation frequency".
Magnetic flux decay output shutoff and magnetic flux decay output shutoff signal
(X74 signal, Pr. 850 = "2")
●
The failure of inverter or increased error in motor may occur due to effect of the motor residual
magnetic flux at the time when the inverter output is shut off when frequent start and stop
(inching operation) is repeated at the time of Real sensorless vector control. If this is the case, set
Pr. 850 = "2" (magnetic flux decay output shutoff ) or turn ON the magnetic flux decay output
shutoff (X74) signal to decay the magnetic flux at a stop, and then shut off the output.
●
With Pr. 850 = "2", deceleration starts at turning OFF of the start command, and the magnetic flux
decay output shutoff is activated when the estimated speed becomes lower than Pr. 10 "DC
injection brake operation frequency".
●
With the brake sequence function is set enabled, the magnetic flux decay output shutoff is
activated when the frequency becomes lower than 0.5 Hz or the Pr. 13 "Starting frequency" setting,
whichever smaller, during deceleration.
●
Inverter output voltage shutoff timing when Pr. 850 = "2"
Maximum time for the magnetic flux decay operation
●
Regardless of the Pr. 850 setting, the magnetic flux decay output shutoff will operate immediately
when the Magnetic flux decay output shutoff signal (X74) is turned ON. For the X74 signal, set "74"
in any of Pr. 178 to Pr. 189 (input terminal function selection) to assign the function.
NOTES
Under Real sensorless vector control, when the X13 signal turns ON while Pr. 11 = "8888", the zero
speed control is activated regardless of the Pr. 850 setting.
When restarting from brake operation at the time of Real sensorless vector control, set Pr. 850 =
"1" (zero speed control). In case of setting value "0" (DC injection brake), it may take approximately
2 s from the time the start up command is input until it actually is output.
I002170E, I002171E
Fig. 5-330:
Inverter output voltage shutoff timing during normal operation and during brake sequence
ON
Start command
(STF, STR)
Speed command
(rotation per
second)
Pr. 10 "DC injection
brake operation
frequency"
Magnetic flux decaying
RUN
RY2
Mechanical brake
MC on the output side
Output voltage
ON
ON
ON
Magnetic flux decay
processing time
Do not turn OFF MC
during this period
ON
Do not turn OFF MC
during this period
ON
Normal operation
During brake sequence
ON
Start command
(STF, STR)
Speed command
(rotation per
minute)
Pr. 13 "Starting
frequency" or 0.5 Hz
(whichever is lower)
Magnetic flux decaying
RUN
RY2
Mechanical brake
MC on the output side
Output voltage
ON
ON
ON
Magnetic flux decay
processing time
ON
ON
Содержание FR-A800
Страница 2: ......
Страница 4: ......
Страница 22: ...Contents XVIII ...
Страница 30: ...Related manuals Introduction 1 8 ...
Страница 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Страница 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 934: ...Check first when you have a trouble Protective functions 6 46 ...
Страница 954: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 1030: ...EC Declarations of Conformity Appendix A 46 A 5 EC Declarations of Conformity A 5 1 Low Voltage Directive ...
Страница 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Страница 1032: ...EC Declarations of Conformity Appendix A 48 ...
Страница 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Страница 1034: ...EC Declarations of Conformity Appendix A 50 ...
Страница 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Страница 1036: ...EC Declarations of Conformity Appendix A 52 ...
Страница 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Страница 1038: ...EC Declarations of Conformity Appendix A 54 ...
Страница 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Страница 1040: ...EC Declarations of Conformity Appendix A 56 ...
Страница 1041: ......