Speed control under Real sensorless vector control, vector control, PM sensorless vector control
Parameters
5 - 82
5.3.3
Setting procedure of PM sensorless vector control (speed control)
This inverter is set for a general-purpose motor in the initial setting. Follow the following procedure
to change the setting for the PM sensorless vector control.
Fig. 5-12:
Setting procedure of PM sensorless vector control (speed control)
PM
PM
PM
Perform IPM parameter initialization. (Refer to page 5-70.)
Set the operation command. (Refer to page 5-263.)
Set "3003 or 3103" in Pr. 998 "PM parameter initialization" or select "3003" in
(IPM parameter initial
settings).
Setting value "3003": parameter settings for MM-CF IPM motor (rotations per minute)
Setting value "3103": parameter settings for MM-CF IPM motor (frequencies)
Select the start command and speed command.
Set parameters such as the acceleration/deceleration time and
multi-speed setting.
Set parameters such as the acceleration/deceleration time
and multi-speed setting as required.
Perform offline auto tuning for a PM motor. (Pr. 96) (Refer to page 5-454.)
Configure the initial setting for the PM sensorless vector control using Pr. 998.
(Refer to page 5-71.)
When the setting for the PM motor is selected in Pr. 998 "PM parameter
initialization", the PM sensorless vector control is selected.
[PM] on the operation panel (FR-DU08) is lit when the PM sensorless vector
control is set.
"8009": Parameter (rotations per minute) settings for an IPM motor other
than MM-CF
"8109": Parameter (frequency) settings for an IPM motor other than MM-CF
"9009": Parameter (rotations per minute) settings for an SPM motor
"9109": Parameter (frequency) settings for an SPM motor
Set "1" (offline auto tuning without rotating motor (for other than
MM-CF)) in Pr. 96, and perform tuning.
Set the motor. (Pr. 9, Pr. 71, Pr. 80, Pr. 81, Pr. 83, Pr. 84 ) (Refer to page 5-434, page 5-454.)
Set "8093 (IPM motor other than MM-CF)" or "9093 (SPM motor)" in
Pr. 71 "Applied motor". Set Pr. 9 "Rated motor current", Pr. 80 "Motor
capacity", Pr. 81 "Number of motor poles", Pr. 83 "Rated motor
voltage, and Pr. 84 "Rated motor frequency" according to the motor
specifications. (Setting "9999 (initial value)" in Pr. 80 or Pr. 81 selects
V/F control.)
Driving a PM motor other than MM-CF
Driving an MM-CF IPM motor
As required for MM-CF
앫
Perform offline auto tuning for a PM motor. (Refer to page 5-454.)
Test run
Содержание FR-A800
Страница 2: ......
Страница 4: ......
Страница 22: ...Contents XVIII ...
Страница 30: ...Related manuals Introduction 1 8 ...
Страница 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Страница 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 934: ...Check first when you have a trouble Protective functions 6 46 ...
Страница 954: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 1030: ...EC Declarations of Conformity Appendix A 46 A 5 EC Declarations of Conformity A 5 1 Low Voltage Directive ...
Страница 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Страница 1032: ...EC Declarations of Conformity Appendix A 48 ...
Страница 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Страница 1034: ...EC Declarations of Conformity Appendix A 50 ...
Страница 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Страница 1036: ...EC Declarations of Conformity Appendix A 52 ...
Страница 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Страница 1038: ...EC Declarations of Conformity Appendix A 54 ...
Страница 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Страница 1040: ...EC Declarations of Conformity Appendix A 56 ...
Страница 1041: ......