28
4
FAILSAFE OF THE SYSTEM WHICH USES THE
INVERTER
When a fault is detected by the protective function, the protective function activates and output a fault signal (ALM). How-
ever, a fault output signal may not be output at an inverter fault occurrence when the detection circuit or output circuit fails,
etc. Although Mitsubishi assures best quality products, provide an interlock which uses inverter status output signals to
prevent accidents such as damage to machine when the inverter fails for some reason.
At the same time consider the system configuration where failsafe from outside the inverter, without using the inverter, is
enabled even if the inverter fails.
Interlock method which uses the inverter status output signals
By combining the inverter status output signals to provide an interlock as shown below, an inverter alarm can be detected.
Backup method outside the inverter
Even if the interlock is provided by the inverter status signal, enough failsafe is not ensured depending on the failure status
of the inverter itself. For example, when the inverter CPU fails, even if the interlock is provided using the inverter fault out-
put signal, start signal and RUN signal output, there is a case where a fault output signal is not output and RUN signal is
kept output even if an inverter fault occurs.
Provide a speed detector to detect the motor speed and current detector to detect the motor current and consider the
backup system such as checking up as below according to the level of importance of the system.
Start signal and actual operation check
Check the motor running and motor current while the start signal is input to the inverter by comparing the start signal to
the inverter and detected speed of the speed detector or detected current of the current detector. Note that the current is
flowing through the motor while the motor coasts to stop, even after the inverter's start signal is turned OFF. For the logic
check, configure a sequence considering the inverter deceleration time. In addition, it is recommended to check the
three-phase current when using the current detector.
Command speed and actual operation check
Check if there is no gap between the actual speed and commanded speed by comparing the inverter speed command
and detected speed of the speed detector.
Interlock Method
Check Method
Used Signals
Refer to
Inverter protective function
operation
Operation check of an alarm contact
Circuit error detection by negative logic
Fault output signal
(ALM signal)
Refer to chapter
"Parameter" of the
Instruction Manual
Inverter operating status
Operation ready signal check
Operation ready signal
(RY signal)
Inverter running status
Logic check of the start signal and
running signal
Start signal
(STF signal, STR signal)
Running signal (RUN signal)
Logic check of the start signal and
output current
Start signal
(STF signal, STR signal)
Output current detection signal
(Y12 signal)
System failure
Inverter
Sensor (speed,
temperature,
air volume, etc.)
To the alarm detection sensor
Controller
Содержание FR-A800
Страница 67: ......