22
INVERTER SETTING
4.2.1 DeviceNet address (Pr. 345)
The definition of
Pr. 345
is as follows.
Parameter
Number
Name
Setting Range
Minimum Setting
Increments
Initial
Value
345
DeviceNet address
0 to 4095
1
63
Bit15 Bit14 Bit13 Bit12
Bit11
Bit10
Bit9
Bit8
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Address Key (AKey)
Not Available
Device Node Address (Addr)
Communication continuation selection(ResCom)
Bit
Item
Initial
Value
Setting
Range
Definition
0 to 5
Device Node
Address (Addr)
63
0 to 63
Node Address (MAC ID) of device
is set between 0 to 63.
Set "63" (initial value) to set node
address with node address switch.
Node address can be set with
DeviceNet Object Class 0x03,
Instance1, Attribute1.
(Refer to
page 50)
11
Selection of
continuous
communication at
inverter reset
(ResCom)
0
0
Reset the option unit in synchronization with the inverter.
When connection is timed out, communication may not resume
according to the master action. In this case, release connection and
reestablish to make communication enabled.
1
The option unit will not be reset even if the inverter is reset and
communication continues.
After inverter reset, preset a value other than "0" in
Pr. 340
so that
the inverter starts in network operation mode.
12 to 15 Address Key (AKey)
0
0
Set "0" always. When a value other than "0" is set, the inverter
operates as when "63" (initial value) is set in
Pr. 345
.