OBJECT DICTIONARY
8.3.14 (Index 4011h) Inverter Status (r)
<Detail>
Read the inverter status.
Bit definitions are as follows.
Sub Index
Item
Description
00h
Name
Inverter Status (r)
Data type
UNSIGNED16 (16 bit unsigned)
Default value
Unit
Access attribute
Read Only
Availability of mapping to PDO Enable
bit
Definition
0
RUN (inverter running)
Signals are not affected by
settings of
Pr.190 to Pr.196
(output terminal function
selection).
1
FWD (During forward rotation)
2
REV (Reverse running)
3
SU (up-to-frequency)
4
OL (overload)
5
IPF (instantaneous power failure)
6
FU (frequency detection)
7
ABC1 (alarm)
8 to 14 (blank)
15
Operation ready completion (READY)