2
Inverter and peripheral devices
1.2 Inverter and peripheral devices
CAUTION
· Do not install a power factor correction capacitor, surge suppressor or radio noise filter on the inverter output side. This will cause the
inverter to trip or the capacitor, and surge suppressor to be damaged. If any of the above devices are connected, immediately remove them.
· This inverter has a built-in AC reactor (FR-HAL) and a circuit type specified in Harmonic suppression guideline in Japan is three-
phase bridge (capacitor smoothed) and with reactor (AC side).
(Refer to page 39)
Do not use an AC reactor (FR-HAL) of a stand-
alone option except following purpose. (Note that overload protection of the converter may operate when a thyristor load is
connected in the power supply system. To prevent this, always install an optional stand-alone AC reactor (FR-HAL).) A DC
reactor (FR-HEL) can not be connected to the inverter.
· Electromagnetic wave interference
The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the communication
devices (such as AM radios) used near the inverter. In this case, connecting a capacitor type filter will reduce electromagnetic
wave interference.
· Refer to the instruction manual of each option and peripheral devices for details of peripheral devices.
Motor
Devices connected to the output
Noise filter (FR-BLF)
Install a noise filter to reduce
the electromagnetic noise
generated from the inverter.
Effective in the range from
about 1MHz to 10MHz. A wire
should be wound four turns at
a maximum.
Three-phase AC power supply
Use within the permissible power supply
specifications of the inverter.
Moulded case circuit breaker (MCCB) or
earth leakage circuit breaker (ELB), fuse
The breaker must be selected carefully
since an in-rush current flows in the inverter
at power on.
Magnetic contactor (MC)
Install the magnetic contactor to ensure
safety. Do not use this magnetic contactor
to start and stop the inverter. Doing so will
cause the inverter life to be shorten.
Do not install a power factor correction capacitor, surge suppressor or radio noise filter on the output
side of the inverter. When installing a moulded case circuit breaker on the output side of the inverter,
contact each manufacturer for selection of the moulded case circuit breaker.
R/L1
S/L2
T/L3
U
W
V
Noise filter
(FR-BLF)
Install a noise filter to reduce the electromagnetic
noise generated from the inverter.
Effective in the range from about 1MHz to 10MHz.
When more wires are passed through, a more
effective result can be obtained. The total number of
wires passed through should be 4T or more.
Earth (Ground)
Earth (Ground)
To prevent an electric shock, always earth (ground) the motor and inverter.
Earth
(Ground)
Capacitor type filter
(FR-BIF)
Reduces the radio noise.
(Refer to page 174)
(Refer to page 3)
(Refer to page 3)
Inverter (FR-A701)
The life of the inverter is influenced by surrounding air temperature. The surrounding air
temperature should be as low as possible within the permissible range. This must be noted
especially when the inverter is installed in an enclosure.
(Refer to page 6)
Wrong wiring might lead to damage of the inverter. The control signal lines must be kept
fully away from the main circuit to protect them from noise.
(Refer to page 12)
Содержание FR-A741-11K
Страница 7: ...MEMO ...
Страница 216: ...209 MEMO ...