1.4.14 Automatic restart after instantaneous power failure selection (CS)
(common)
This function allows the inverter to re-control the motor
automatically when power is restored after an
instantaneous power failure.
do not have CS
signal but have automatic restart after instantaneous power
failure function. (Refer to page 367 for details.)
When the automatic restart after instantaneous power
failure selection signal (CS) is turned ON, automatic restart
operation is enabled.
When [
Pr. 57
9999] (automatic restart operation enabled),
the inverter will not operate if used with the CS signal
remained OFF.
CS signal is also used to switch inverter/bypass operation
when bypass-inverter switchover function is active (Refer to
page 416.)
A700 F700
E700
D700
STF
IM
MCCB
CS
CS
S1/L21
R1/L11
T/L3
S/L2
R/L1
MC1
MC2
W
V
U
MC
switchover
sequence
SD
SD
For use for only
automatic restart
after instantaneous
power failure or flying start,
turn ON CS in advance.
Inverter