2.16 Operation selection at power failure and
instantaneous power failure
2.16.1 Automatic restart after instantaneous power failure/flying start
[Pr. 30, 57, 58, 96, 162, 163*, 164*, 165, 298*, 299, 611]
(common)
When instantaneous power failure protection (E.IPF) and
undervoltage protection (E.UVT) are activated, the inverter
output is shut off. (Refer to page 111 for E.IPF and E.UVT)
When automatic restart after instantaneous power failure
operation is set with the following conditions, the motor can be
restarted if power is restored after an instantaneous power
failure or undervoltage. (E.IPF and E.UVT are not activated.)
• when electronic bypass operation is switched to inverter
operation
• when power comes back ON after an instantaneous
power failure
• when motor is coasting at start
Automatic restart after instantaneous power failure function is
invalid when load torque high speed frequency control ([
Pr.
270
= 2, 3]) is set.
common
(*[
Pr. 163, 164
] are not available for
.)
(*[
Pr. 298
] is not available for
.)
E700
D700
A700
F700
[Pr. ]
Name
Initial Value
Setting Range
Description
Available Inverters
57
Restart
coasting time
9999
0
1.5K or less ..... 0.5s
2.2K to 7.5K .... 1s
11K to 55K....... 3.0s
75K or more .... 5.0s
of coasting time
1.5K or less...... 1s
2.2K to 7.5K.....2s
11K or more .....3.0s
of coasting time
{
{
{
{
55K or
less
0.1 to 5s
Set the waiting time for inverter-triggered
restart after an instantaneous power failure.
75K or
more
0.1 to 30s
9999
No restart
58
Restart
cushion time
1s
0 to 60s
Set a voltage starting time at restart.
{
{
{
{
96
Auto tuning
setting/status
0
0
Offline auto tuning is not performed.
{
*
—
{
{
1
For Advanced magnetic vector control
Offline auto tuning (all motor constants)
without running the motor.
(Refer to page 268)
{
*
—
{
—
11
For General-purpose magnetic flux vector
control
Offline auto tuning (only motor constant (R1))
without turning the motor.
(Refer to page 268)
—
—
{
{
21
For V/F control.
Offline auto tuning (without running the
motor) for automatic restart after
instantaneous power failure (with frequency
search)
—
—
{
{
101
For Advanced magnetic vector control
Offline auto tuning (all motor constants) by
running the motor.
(Refer to page 268)
{
*
—
—
—
162
Automatic
restart after
instantaneous
power failure
selection
0
0
With frequency search
{
{
{
{
1
Without frequency search (reduced voltage
system)
{
{
{
{
2
Encoder detection frequency search
{
—
{
—
10
Frequency search at every start
{
{
{
{
11
Reduced voltage at every start
{
{
{
{
12
Encoder detection frequency search at every start
{
—
{
—
A700
F700
E700
D700
A700
F700
E700
D700