Maintenance and inspection
Measurements on the main circuit
FR-A700 EC
8 - 15
8.2
Measurements on the main circuit
This section describes the measurement of the main circuit voltages, currents, powers and in-
sulation resistance.
8.2.1
Insulation resistance test using megger
For the inverter, conduct the insulation resistance test on the main circuit only as shown below
and do not perform the test on the control circuit. (Use a 500V DC megger.).
8.2.2 Pressure
test
Do not conduct a pressure test. Deterioration may occur.
I001312E
Fig. 8-14:
Insulation resistance test
b
CAUTION:
Before performing the insulation resistance test on the external circuit, disconnect
the cables from all terminals of the inverter so that the test voltage is not applied to
the inverter.
NOTE
For the continuity test of the control circuit, use a tester (high resistance range) and do not
use the megger or buzzer.