Wiring
Control circuit specifications
FR-A700 EC
3 - 29
3.4.4 Wiring
instructions
●
Terminals 5, PC and SE are common to the I/O signals and isolated from each other. Do
not earth (ground). Avoid connecting the terminal PC and 5 and the terminal SE and 5.
●
Use shielded or twisted cables for connection to the control circuit terminals and run them
away from the main and power circuits (including the 200V relay sequence circuit).
●
Use two or more parallel micro-signal contacts or twin contacts to prevent a contact faults
when using contact inputs since the control circuit input signals are micro-currents.
●
Do not apply a voltage to the contact input terminals (e.g. STF) of the control circuit.
●
Always apply a voltage to the alarm output terminals (A, B, C) via a relay coil, lamp, etc.
●
It is recommended to use the cables of 0.75mm² gauge for connection to the control circuit
terminals.
●
If the cable gauge used is 1.25mm² or more, the front cover may be lifted when there are
many cables running or the cables are run improperly, resulting in an operation panel contact
fault.
●
The wiring length should be 30m maximum.
Wiring of the control circuit of the 02160 or more
For wiring of the control circuit of the 02160 or more, separate away from wiring of the main cir-
cuit. Make cuts in rubber bush of the inverter side and lead wires.
Fig. 3-20:
Contacts
I001021E
I001022E
Fig. 3-21:
Wiring of the control circuit of the 02160 or more
Micro signal contacts
Twin contacts
Wiring
Make cuts along the lines inside with a cutter
knife and such.
Rubber bush
(view from the inside)
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......