Parameter
Selection and protection of a motor
FR-A700 EC
6 - 217
PTC thermistor input (PTC signal)
PTC thermistor output built-in the motor can be input to the PTC signal (AU terminal).
For the terminal used for PTC signal input, assign the function by setting "63" to Pr. 184 "AU ter-
minal function selection" and also set the AU/PTC switchover switch to the PTC terminal func-
tion. (The initial setting is the AU terminal function.)
If a motor overheat state is detected for more than 10s according to the input from the PTC ther-
mistor, the inverter shuts off the output and outputs the PTC thermal alarm signal (E.PTC).
The table below shows the correspondence between the motor temperature and the PTC ther-
mistor resistance values:
Fig. 6-92:
Connection of a PTC thermistor
I001140E
Fig. 6-93:
AU/PTC switchover switch
I001141E
Motor Temperature
PTC Thermistor Resistance Value [
Ω
]
Normal
0 to 500
Boundary
500 to 4k
Overheat
4k or higher
Tab. 6-45:
Working area of the PTC function
NOTES
When the PTC signal was not assigned to Pr. 184 and the AU/PTC switchover switch was
set to the PTC terminal function, the function assigned to the AU terminal is always off.
Reversely, when the PTC signal was assigned to Pr. 184 and the AU/PTC switchover switch
was set to the AU terminal function, a PTC thermal error (E.PTC) occurs since the function
is always in a motor overheat state.
When you want to input a current, assign the AU signal to the other signal.
When terminal assignment is changed, the other functions may be affected. Please make
setting after confirming the function of the AU terminal.
SD
Inverter
Inverter
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......