Main speed setting
3.9.3
Main speed command by terminal JOG single-phase pulse train input
(Pr. 384 to Pr. 386, Pr. 703, Pr. 704)
At JOG input (single-phase pulse train input), input from terminal JOG is converted to main rotation speed frequency (Hz).
Pulse input unit (kpps)
main rotation speed frequency (Hz)
The following shows conversion methods of pulse input, which is input to terminal JOG, to a main rotation speed frequency.
Set
Pr. 384 Input pulse division scaling factor
= "1"
Parameter
Number
Name
Setting Range
Increments
Initial Value
384
Input pulse division scaling factor
0 to 250
1
0
385
Frequency for zero input pulse
0 to 400Hz
0.01Hz
0Hz
386
Frequency for maximum input pulse
0 to 400Hz
0.01Hz
60Hz
703
Minimum number of input pulse
0 to 100kpps
0.01kpps
0kpps
704
Maximum number of input pulse
0 to 100kpps
0.01kpps
100kpps
Frequency
[Hz]
Input pulse
[kpps]
400
Frequency
[Hz]
Input pulse
[kpps]
0
0
Frequency
[Hz]
Input pulse
[kpps]
0
Frequency
[Hz]
Input pulse
[kpps]
0
1)
Pr. 385 < Pr. 386, Pr. 703 < Pr. 704
2)
Pr. 385 > Pr. 386, Pr. 703 < Pr. 704
3)
Pr. 385 < Pr. 386, Pr. 703 > Pr. 704
4)
Pr. 385 > Pr. 386, Pr. 703 > Pr. 704
400
400
400
Pr.386 (Frequency for
maximum input pulse)
Pr.386 (Frequency for
maximum input pulse)
Pr.385 (Frequency for
zero input pulse)
Pr.386 (Frequency for
maximum input pulse)
Pr.385 (Frequency for
zero input pulse)
Pr.385 (Frequency for
zero input pulse)
Pr.386 (Frequency for
maximum input pulse)
Pr.385 (Frequency for
zero input pulse)
Pr. 703
(Minimum number
of input pulses)
Pr. 704
(Maximum
number of input pulse)
Pr. 703
(Minimum number
of input pulses)
Pr. 704
(Maximum
number of input pulse)
Pr. 703
(Minimum number
of input pulses)
Pr. 704
(Maximum
number of input pulse)
Pr. 703
(Minimum number
of input pulses)
Pr. 704
(Maximum
number of input pulse)